5 Installation
5.4 Preparing the device for operation
MICRO PANEL XP-702
07/2011 MN04802003Z-EN
www.eaton.com
51
5.4.5
Mounting a device with a display
1
Select the mounting position of the device as described in Chapter 5.2.2 Requirements for the
mounting position,
2
Prepare a mounting cutout for the device at the selected position:
Mounting cutout:
8.4" devices: 261
×
194 mm (±1 mm)
10.4" devices: 329
×
238 mm (±1 mm)
12.1" devices: 344
×
262 mm (±1 mm)
15" devices: 410
×
315 mm (±1 mm)
Material thickness at the mounting cutout 2…5 mm
The following number of retaining brackets and threaded pins are required for mounting
in accordance with IP65 / NEMA 4X and for use in potentially explosive atmospheres:
8.4", 10.4" and 12.1" devices: 8 pieces each
15" devices: 12 pieces each
If needed, please order additional retaining brackets with threaded pins from your sup-
plier.
Fig. 33 Mounting cutout for 8.4" devices
Fig. 34 Mounting cutout for 10.4" devices
Fig. 35 Mounting cutout for 12.1" devices
Fig. 36 Mounting cutout for 15" devices
261.0
+1/-1
194.0
+1/-1
329.0
+1/-1
238.0
+1/-1
344.0
+1/-1
262.0
+1/-1
410.0
+1/-1
315.0
+1/-1
www.comoso.com