28 XN-322-8AIO-I analog input/output module
28.4 Technical data
XN300 slice modules
06/16 MN050002 EN
www.eaton.com
217
28.4.2 Analog outputs
28.4.3 External power supply
The 24 VDC power supply is used to power the analog inputs and outputs.
Software (parameterizable)
parameterizable
Open wire monitoring
Yes
Measuring accuracy
Total error limit
±0.5% of full scale value
Channels
Value
Channels
Value
Number of channels
4 analog output channels
Measuring range
0…20 mA
Measured value
0…20000
D-A converter
12 Bit
Resolution
5
μ
A / LSB
Conversion time per channel
1 ms
Load resistance (burden)
0 < R
burden
< 500
Ω
Max. permissible output capacitance
1
μ
F with 50
Ω
burden
Open wire monitoring
No
Settling time (typical) for
63% of end value
50
μ
s + R
burden
∙
R
L capacitive
86% of end value
100
μ
s + 2
∙
R
burden
∙
R
L capacitive
99% of end value
250
μ
s + 5
∙
R
burden
∙
R
L capacitive
Measuring accuracy
Total error limit
±0.5% of full scale value
Channels
Value
Number of supply voltages
1 (X5, pin on connector 24V)
Supply v24 V
18…30 VDC
Voltage monitoring
Supply voltage OK status LED
U > 18 VDC
Maximum current consumption
70 mA
Summary of Contents for XN300