Xiria
6
994.570 G01 06
1.4 Product standards and guidelines used
Table 1: Current product standards used
Standard
Title
IEC62271-1
Common specifications for high-voltage switchgear and control gear standards
IEC62271-100
High-voltage alternating-current circuit-breakers
IEC62271-102
Alternating current disconnectors and earthing switches
IEC62271-103
High-voltage switches
IEC62271-200
A.C. metal-enclosed switchgear and control gear for rated voltages above 1 kV and up to and including 52 kV
IEC62271-304
Additional requirements for enclosed switchgear and control gear from 1 kV to 72.5 kV to be used in severe
climatic conditions
IEC60529
Degrees of protection provided by enclosures
IEC61869-2
Instrument transformers - Part 1: Current transformers
IEC61869-3
Instrument transformers - Part 2: Inductive voltage transformers
EN50181
Plug-in type bushings above 1 kV up to 36 kV
ISO 9001-2000
Quality
ISO 14001
Environmental management
1.5 Product information
The unit is equipped with type plates on the inside walls of
the cable connection compartments (see Figure 1-1 to
Figure 1-6).
The panel type plate includes:
switch type;
technical specifications;
serial number and year of manufacture.
Eaton Industries (Netherlands) BV
Medium Voltage
P.O. box 23, 7550 AA Hengelo,
The Netherlands
M.V. SWITCHGEAR
IEC 62271-200
system:
XIRIA
r2.9
AIR INSULATED
w.o. no.:
539660
Serialno: 1034XIRA290850041
Year of man.:
2010
U
r
24
kV
U
p
125
kV
U
d
50
kV
f
r
50/60
Hz
I
r
630
A
I
k
16
kA
I
p
40
kA
t
k
1
s
IAC AFL
Ua 24 VDC
Main switching device: 16kA-1s
Figure 1-1: Example of system type plate
CIRCUIT-BREAKER
IEC 62271-100
type: NVR12AA-2402 R2.9
U
r
24 kV
U
p
125 kV
I
r
200 A
I
k
16 kA
t
k
0.6 s
I
c
31.5 A
I
sc
16 kA
DC
component
35%
L
ma
16 kA
U
a
24 VDC
Operating sequence O-3 min-CO-3 min-CO
Classification E2 C2
GENERAL PURPOSE SWITCH
IEC 62271-102
type: SVR14AA-2406 R2.9
U
r
24 kV
U
p
125 kV
I
r
630 A
I
k
16 kA
t
k
1 s
I
ma
16 kA
I
1
630 A
I
2a
630 A
I
4a
31.5 A
I
6a
240 A
I
6b
55 A
n
100
U
a
24 VDC
Classification E3
For more information refer to main nameplate
Figure 1-2: Example of panel type plate for
circuit-breaker
Figure 1-3: Example of panel type plate for load-break switch
Summary of Contents for xiria series
Page 39: ...Xiria 994 570 G01 06 39 APPENDIX 1 FLOOR PLANS...
Page 40: ...Xiria 40 994 570 G01 06...
Page 41: ...Xiria 994 570 G01 06 41...
Page 42: ...Xiria 42 994 570 G01 06...
Page 43: ...Xiria 994 570 G01 06 43...
Page 44: ...Xiria 44 994 570 G01 06...
Page 45: ...Xiria 994 570 G01 06 45 APPENDIX 2 VOLTAGE DETECTING SYSTEM WEGA...
Page 46: ...Xiria 46 994 570 G01 06...
Page 47: ...Xiria 994 570 G01 06 47...
Page 48: ...Xiria 48 994 570 G01 06 APPENDIX 3 ORION 3 0...
Page 49: ...Xiria 994 570 G01 06 49 APPENDIX 4 SHORT CIRCUIT INDICATOR...
Page 55: ...Xiria 994 570 G01 06 55...
Page 56: ...Xiria 56 994 570 G01 06...