background image

Chapter 2.1.1. – 2

EATON CORPORATION

xxxxx+xxxx-xxxxEN

Residual Current Devices

Tripping Characteristics (IEC/EN 61008)

§ 6.1.1 of ÖVE/ÖNORM E 8001-1/A1

deals with 

additional pro-

tection 

and provides essentially the following: 

In circuits with 

sockets up to 16 A

with fault current/residual current

protection by protective earthing, protective multiple earthing or
residual current devices (RCDs), additional residual current protection
devices with a rated tripping current of 

0.03 A

must be installed.

This means when using RCDs for fault current/residual current
protection two RCDs must be connected in series.

Testing:

RCDs with tripping time delay (Types -G and -S) may be function test-
ed with conventional testing equipment which must be set according
to the instructions for operation of the testing device. Due to reasons
inherent in the measuring process, the tripping time determined in
this way may be longer than expected in accordance with the specifi-
cations of the manufacturer of the measuring instrument. 
However, the device is ok if the result of measurement is within the
time range specified by the manufacturer of the measuring instru-
ment.

Tripping characteristics, tripping time range and selectivity of instantaneous,
surge current-proof "G" and surge current-proof - selective "S" residual cur-
rent devices.

T

ripping time t

Tripping time range type S

Residual tripping current 

surge current.-
proof - selective

surge current-
proof

conditionally
surge current-
proof

Tripping time range type G

Tripping time range limit values

Tripping time range non-delayed

Area of unwanted tripping 

Summary of Contents for xEffect

Page 1: ...G min 10 ms time delay surge current proof up to 3 kA For system components where protection against unwanted tripping is compulsory to avoid personal injury and damage to property 12 1 6 of VE NORM E...

Page 2: ...ntional testing equipment which must be set according to the instructions for operation of the testing device Due to reasons inherent in the measuring process the tripping time determined in this way...

Page 3: ...s to an enormous increase in the reliability of systems Therefore we recommend to use frequency converter proof RCDs These special residual current devices can be recognised by an extension of the typ...

Page 4: ...e of leakage currents Integrated auxiliary contact Local Indication New level of accuracy reduced unwanted tripping No monthly test required Comprehensive range of accessories Real contact position in...

Page 5: ...ay application type R 4 pole 63 0 03 FRCdM 63 4 003 R 168636 1 30 SG49712 In I n Type Article No Units A Designation per package Residual Current Devices FRCdM type S A Selective surge current proof t...

Page 6: ...pole device can also be used for 2 pole connection See connection possibilities The test key T must be pressed every year The system operator must be informed of this obligation and his responsibilit...

Page 7: ...ive surge current proof Electrical isolation 4 mm contact space Maximum back up fuse Short circuit and overload protection In 16 63A 63 A gG gL In 80A 80 A gG gL In 100A 100 A gG gL Endurance electric...

Page 8: ...shing yellow red Check the device with test key If the LEDs are still flashing check the direction of connection supply side load side Remote Indication Potential free auxiliary switch for use in cont...

Page 9: ...ndication through 3 LEDs B types also meet the requirements of superior fire protection systems according to VDE 0664 400 formerly known as VDE V 0664 110 4 pole types can also be used as 2 pole devic...

Page 10: ...7900 1 30 40 0 3 FRCdM 40 4 03 S B 167901 1 30 63 0 3 FRCdM 63 4 03 S B 167902 1 30 SG49812 In I n Type Article No Units A Designation per package Residual Current Devices FRCdM Typ G B Surge current...

Page 11: ...1 30 40 0 3 FRCdM 40 4 03 G Bfq 167905 1 30 63 0 3 FRCdM 63 4 03 G Bfq 167906 1 30 SG49812 In I n Type Article No Units A Designation per package Residual Current Devices FRCdM Typ S Bfq Selective su...

Page 12: ...residen tial and similar applications Under all other conditions e g damp ly or dusty environment it s recommended to test in shorter inter vals e g monthly A test is further needed if red and yellow...

Page 13: ...Type S B S B and S Bfq typ 5 kA 8 20 s selective surge current proof Electrical isolation 4 mm contact space Maximum back up fuse Short circuit and overload protection In 16 63A 63 A gG gL In 80A 80...

Page 14: ...of connection supply side load side Remote Indication Potential free auxiliary switch for use in control circuits insulated from main circuit of the switch gear according to IEC EN60664 0 25A ohmic l...

Reviews: