Eaton VICKERS DG3V-10 Series Overhaul Manual Download Page 13

13

Figure 11. DG5V10 with DG4S4-01 Pilot

Section IV - Pilot Valve Section 

A. Spool Type - Pilot Valve Section

To maintain proper control, closed center pilot spools are
normally used in two stage valves. In most cases, a number
‘‘6’’ type pilot spool is used.

When a type ‘‘4’’ or ‘‘8’’ main stage spool is used, the letter
‘‘V’’ is inserted into the pilot valve model code.

B. Spool Positioning - Pilot Valve Section

Pilot spools are positioned within the valve by special spool
arrangements. The three basic pilot valve spool arrangements
are spring centered, spring offset and detents. The following
paragraphs (1 through 3) describe pilot spool arrangements.

1. Spring Centered: A spring and washer are installed at
each end of the pilot valve spool. The spring moves the
spool until the washer contacts the end of the valve body. In
the deenergized condition of the pilot valve, the spool is held
in center position within the body by the springs and washers.

2. Spring Offset: Spring offset models use one spring and
washer to return the pilot valve spool to an offset position. In
this model, a solenoid is completely removed from the spring
end of the pilot valve. Solenoid operating power is reduced
by the sacrifice of the center spool position.

3. Detents: A detent mechanism is installed on one or both
ends of the pilot valve spool. Detent valve solenoids can be
momentarily energized to the correct position and then power
may be removed from the solenoid. This reduces the input
control power below that of an offset model.

The detent(s) hold the pilot spool in the last position attained
until the opposite solenoid is energized. As in the offset
valve, solenoid power is reduced by the sacrifice of the
center spool position.

C. Methods of Control - Pilot Valve

The following pilot control methods are available for pilot
spool position.

Control

Model Codes

Electrical Solenoid

DG4S4-01, DG4V-3, DG4V-3S

1. Remote Pilot: Pilot valves, such as a DG3V3, are
available for use with a remote pilot source. This means that
a valve can be shifted from a remote pressure source by
other valves in the logic circuit. Refer to service parts
drawings listed in Table 1.

2. Electrical Solenoid Pilot Operation: Electrical solenoids
are attached to the pilot valve body. Internal push pins
connect the solenoid to the pilot spool. When the magnetic
field of solenoid ‘‘B’’ is energized, the solenoid armature
moves the push pin and shifts the pilot spool towards
solenoid ‘‘A’’ (see Figure 12a). When solenoid ‘‘A’’ is
energized, the pilot spool shifts toward solenoid ‘‘B’’ (see
Figure 12b). When both solenoids are de-energized, the pilot
spool shifts to center position (see Figure 12c).

Summary of Contents for VICKERS DG3V-10 Series

Page 1: ...5007 01 EN 1099 M DG3V 10 DG5V 10 Solenoid Pilot Operated Overhaul Manual VICKERS Directional Control Valves...

Page 2: ...peration 7 Section IV Pilot Valve Section 13 Section V Internal Valve Functions 15 Section VI Installation 16 Section VII Service Inspection Maintenance 18 Section VIII Overhaul 19 DG5V 8 S H C 10 25...

Page 3: ...contained in this manual The parts and installation drawings listed in Table 1 are available from any Vickers Distributor C Model Codes Variations within each basic model series are covered in the mod...

Page 4: ...psi See spool spring combinations below Left Hand Build L A Models only omit if not required Fast Response X Not available with CETOP 3 pilots or pressure centered D and DB models Spool Control Modif...

Page 5: ...els 2 7 If both are required available on A B C N models 2 8 If both are required available on AL B C N D models CAUTION Stroke adjust pilot pressure models are rated to a maximum of 210 bar 3000 psi...

Page 6: ...ports are open or closed See Figure 1 Oil flow is directed from one port to another within the body and out of a port to the work C Two Stage Directional Valve Construction Two stage directional valv...

Page 7: ...ked and the cylinder is held in a definite position In some circuits flow from the tank port is piped into the pressure port of another valve This allows the same source of power to operate two differ...

Page 8: ...the center position A B P T Closed Center Bleed A B T A P B F Type 52 spool A B P T Closed Center Regen by Solenoid A T A P B G Type 521 spool A B P T Closed Center Regen by Solenoid B T A P B H Type...

Page 9: ...ol can move from its last position under the influence of gravity or tank line pressure This must be considered during the design of the system Units with floating type spools have the model code lett...

Page 10: ...to the sleeve and piston areas on the left side but the sleeve is bottomed against the valve body at this time Only the piston area applies force to the left end of the spool Since the spool land are...

Page 11: ...t To limit the spool travel loosen the jam nut and turn adjusting screw clockwise Figure 8 Stroke Adjuster Feature 2 7 5 1 3 4 6 Main Stage Spool Part No Part Name 1 2 3 4 Cover Spring O Ring Back up...

Page 12: ...Dowel Pin Figure 10 Reducer Module Table 2 Shift Response Times w CETOP 3 Pilot Fast Response option not available Valve Type Condition Pilot Pressure 10 bar 150 psi Pilot Pressure 100 bar 1500 psi P...

Page 13: ...l position 3 Detents A detent mechanism is installed on one or both ends of the pilot valve spool Detent valve solenoids can be momentarily energized to the correct position and then power may be remo...

Page 14: ...Solenoids DG4S4 01 pilot valves are usually equipped with air gap solenoids Air gap solenoids are isolated from system fluid and can be removed and replaced without disturbing the system A push pin a...

Page 15: ...a D Brad Harrison Connectors Brad Harrison connectors thread into the 1 2 NPTF opening in the wiring housing of a DG4V 3 or a DG4S4 01 directional valve PA3 A prefix of PA3 in the model code indicates...

Page 16: ...CAN overcome pilot pressure Drain connection Y is used for externally drained models Pressure centered D models use two drain connections Y and W All external drain connections MUST be piped directly...

Page 17: ...he necessary fittings and connections required for proper installation 3 The number of bends in tubing should be kept to a minimum to prevent excessive turbulence and friction of fluid flow Tubing mus...

Page 18: ...ntenance E Replacement Parts Reliable operation throughout the specified operating range is assured only if genuine Vickers parts are used Sophisticated design processes and material are used in the m...

Page 19: ...Slight variations may be noted on your model depending on the type of accessories and unit design Figure 15 may be used for all models except pressure centered D models regardless of the design Refer...

Page 20: ...emove four screws 3 and crossover plate from main stage body 6 3 Remove and discard two O rings 5 from crossover plate Note The following section pertains to main stage disassembly If your unit does n...

Page 21: ...18 and O ring 19 from core tube S A 20 Discard O Ring 19 6 Remove pilot spool 21 from body 5 7 Remove plugs 24 and 22 and O Ring 23 from body 5 Discard O Ring 23 8 Secure the body and remove plugs 25...

Page 22: ...voltage rating of the coil Refer to Table 8 This test is superficial but a more rigorous test requires special equipment If the coil seems to be burned or extreme heat is encountered during operation...

Page 23: ...Make sure the spool moves freely inside the body bore and is oriented properly See parts drawing 7 Install piston 12 sleeve 11 and spring 10 into cover 8 8 Install O ring 9 in cover and install cover...

Page 24: ...stop 16 spring 17 and push pin 18 on spool 21 4 Install O ring 19 on core tube S A 20 and install core tube S A into body 5 5 Install O ring 9 on core tube S A 20 6 Install gasket 14 and coil 10 on bo...

Page 25: ...at 1 3 Pilot Choke 1 18 Poppet 1 4 Reducer 1 19 Spring 1 5 Body 1 20 Sleeve 1 6 O Ring 9 21 Plug 4 7 Screw 4 22 O Ring 11 8 Adapter Plate 1 23 Plug 10 9 Plug 1 24 O Ring 2 10 Screw 8 25 O Ring 4 11 Co...

Page 26: ...5 O Ring 1 2 Name Plate 1 16 Screw 4 3 Screw 4 17 Cover 1 4 Cover Plate 1 18 O Ring 1 5 O Ring 2 19 Spring 1 6 Body 1 20 Washer 1 7 Screw 4 21 O Ring 2 8 Cover 1 22 O Ring 3 9 O Ring 1 23 Plug 13 10 S...

Page 27: ...Nameplate 1 15 O Ring 2 3 Cover 1 16 O Ring 1 4 Gasket 1 17 Push Pin 1 5 Terminal Box 1 18 Spring 1 6 Gasket 1 19 Washer DC models 2 7 Screw 2 20 Washer AC models 2 8 Strap 1 21 Core Tube S A 1 9 Scr...

Page 28: ...1 22 Plug 1 8 Knob 2 23 O Ring 1 9 O Ring 2 24 Plug 1 10 Coil Type A 2 25 Plug 1 11 DIN Coil 2 26 O Ring 1 12 Plug 2 27 Plug 1 13 DIN Receptacle 2 28 O Ring 1 14 Gasket 2 29 O Ring 5 15 Washer 2 Figu...

Reviews: