Air circuit breakers with PXR trip units -   

PXR rated current 

(

I

n

marking change

  

EATON

 www.eaton.com

Section 1: Introduction

Air circuit breakers with PXR electronic trip units are pre-configured 

at the factory for their rated current (

I

n

).  This software allows you 

to modify the 

I

n

 within a restricted range.  The allowable 

I

n

 ratings 

are determined by a combination of factors including the breaker’s 

construction and the breaker’s application.  This software will restrict 

the 

I

 to the values supported by the circuit breaker’s construction.  

You are responsible to limit the 

I

n

 value based on the application and 

not exceed any value specified by the engineer responsible for the 

installation.
Protection settings of the trip unit are based on the 

I

n

 rating.  These 

settings affect the time-current curves and contribute to proper sys-

tem coordination.  Modification of the 

I

n

 may require re-evaluation 

of the circuit breaker’s protection settings and overall coordination 

study to ensure proper application by the engineer responsible for 

the installation.
The 

Change PXR ACB Rated Current functionality in PXPM

 is used in 

place of the rating plugs used in Digitrip trip units.
This Instruction Leaflet provides instructions for updating the current 

marking on the breaker after making a change to the rated current 

(

I

n

) using PXPM and the licensed 

Change PXR ACB Rated Current

 

functionality.  The user is responsible for updating the rated current 

(

I

n

) marking on the breaker frame to match new rated current (

I

n

)  to 

ensure compliance with regulatory bodies.

Figure 1. PXR rated current marking component overview  

(Magnum  shown).

PXR trip unit

Frame rating 

module

I

n

 rating

Section 2: Replacing the rated current label

ote: 

N

A number of graphics in these instructions use the Magnum frame 

breaker only as typical examples.  The PD-RF and PD-NF breakers are similar 

in those situations.

Step 1. 

Peel the factory In label from the Frame Rating Module 

cover.

Step 2. 

Find the label corresponding with the new rated current 

(

I

n

) programmed through PXPM. These labels are included 

as part of PXPM-SW-PXRIN-KIT-1, along with the license to 

make one change to a breaker’s rated current.

Figure 2. Step 2. Provided label sheet 

Step 3. 

Place label over the rated current (

I

n

) marking located on the 

trip unit such that the previous marking is no longer visible.

Figure 3. Step 3. Placing label

ote: 

N

A blank white field is provided on the Frame Rating Module cover 

beneath the factory rated current label. If the correct rated current label is not 

available at the time of reprogramming, remove the factory rated current label 

and mark the new rated current on the white field with a permanent marker. 

Contact Eaton for new rated current labels and apply the correct label when 

available. 

70C2131H01

I

  

=6300

I

  

=5000

I

  

=3800

I

  

=3200

I

  

=2500

I

  

=1600

I

  

=2000

I

  

=3000

I

  

=3600

I

  

=4000

I

  

=6000

I

  

=100

I

  

=200

I

  

=250

I

  

=300

I

  

=500

I

  

=630

I

  

=1000

I

  

=1250

I

  

=1200

I

  

=800

I

  

=600

I

  

=400

n

n

n

n

n

n

n

n

n

n

n

n

n

n

n

n

n

n

n

n

n

n

n

Place label 

here.

*Cover not shown for clarity.

Reviews: