Installation of conduits and grounding of equipment enclosures. 
These enclosures are intended for wall mounting only!

 Connection of metallic and non-metallic conduits
 Verbindung von metallischen und 

nicht-metallischen Installationsrohren

 Raccordement de tubes conducteurs métalliques

et non-métalliques

 Conexión de conductos metálicos y no metálicos

conductos

 Maximum permissible size of conduit entry
 Maximal zulässige Größe der Installations-

rohreinführung

 Entrée de câbles max. admise
 Tamaño máximo admisible de la entrada del

conducto

National Electric Code (N.E.C. – USA) 
Canadian Electric Code (C.E.C. – Canada)

2 x ½“ conduit – 2 x ½“ Installationsrohr – 
2 x ½“ canalisation – 2 x ½“ conducto

a

Connector hub

b

Use trade size conduit fittings

c

Grounding conductor

d

Equipment grounding terminal

e

Locknut

Conduit trade size

inches

½

¾

1

1 – ¼

1 – ½

Hole diameter

inches

7

/

8

1 – 1

1

/

8

1 – 1

3

/

8

1 – ¾

2

mm

22

28

35

44

50

On-Off switches 

On-Off switches (Complete rotation in both directions)

 + 

Change over switches with 

OFF

-Position

Change over switches with 

OFF

-Position (Pulse contact with spring return)

Change over switches without 

OFF

-Position

Voltage-Ammeter selector switches

Position

Voltage

Current

Star-delta switches

Wattmeter selector switches

Reversing switches

Fractional HP MotorReversing (auxiliary winding)

Reversing star-delta switches

1

2

3

en

de

fr

es

en

de

fr

es

a

e

d

c

b

WARNING

Empty enclosures and enclosures used 
with switches for the North American 
market have no knock-outs in the end 
walls of the enclosure. Conduit entries 
must be drilled to suit as shown. 
The metric size conduit entries which 
appear in product dedicated IL… 
Instruction Leaflet supplied with 
enclosed switches do not apply to 
North American switch enclosures.

en

en

WARNING

First secure the connector hub onto the conduit. 
Then secure conduit with connector hub into the enclosure hole, using the locknut for fixing. 
Bonding and grounding bushings are not required.