STEP 2 (Continued)

Basic Application Default I/O Configuration 

GND terminals 3, 7 and 13 are internally connected.

For the STANDARD Application, input signals at DIN1 and DIN2 are 
programmed as a pair using parameter 2.1.

Connect CMA/CMB inputs to either logic high or logic low depending 
upon your application. Refer to the 

SVX9000 User Manual

 and 

SVReady Application Manual

 for additional information.

Maximum Switching Voltage: 300V DC, 250V AC
Maximum Switching Load: 8A/24V DC; 0.4A/250V DC; 2 kVA/250V AC
Maximum Continuous Load: 2A rms

Terminal

Signal

Description

NXOPTA9

1

+10V

ref

Reference output Voltage for potentiometer, etc.

2

AI1+

Analog input, 
voltage range 
0 – 10V DC

Voltage input frequency 
reference

3

AI1-

I/O Ground

Ground for reference and 

controls

4

AI2+

Analog input, 
current range 
0 – 20 mA

Current input frequency 
reference

5

AI2-

6

+24V

Control voltage 
output

Voltage for switches, etc. 
max 0.1A

7

GND

I/O ground

Ground for reference and 

controls

8

DIN1

Start forward

Contact closed = start forward

9

DIN2

Start reverse

Contact closed = start reverse

10

DIN3

External fault 
input
(programmable)

Contact open = no fault
Contact closed = fault

11

CMA

Common for 
DIN 1 – DIN 3

Connect to GND or +24V

12

+24V

Control voltage 
output

Voltage for switches 
(see terminal 6)

13

GND

I/O ground

Ground for reference and 
controls

14

DIN4

Multi-step speed 
select 1

DIN4

DIN5

Frequency
ref.

15

DIN5

Multi-step speed 
select 2

Open
Closed

Open

Closed

Open
Open

Closed

Closed

Ref.V

in

Multi-step
ref.1
Multi-step
ref.2
Ref

Max

16

DIN6

Fault reset

Contact open = no action
Contact closed = fault reset

17

CMB

Common for 
DIN4 – DIN6

Connect to GND or +24V

18

AO1+

Output frequency
Analog output

Programmable
Range 0 – 20 mA, R

L

 max. 

500

1

19

AO1-

20

DO1

Digital output
READY

Programmable

Open collector, 

I

)

 50 mA, 

V

)

 48V DC

NXOPTA2

21

RO1

Relay 
output 1 

RUN

22

RO1

23

RO1

24

RO2

Relay 
output 2 

FAULT 

25

RO2

26

RO2

Remote reference
0(4) – 20 mA

READY

Reference potentiometer
1 – 10 k

1

mA

RUN

 

MN04003009E.fm  Page 5  Thursday, February 17, 2005  11:59 AM

Summary of Contents for SVX900

Page 1: ...poration CONTENT STEP 1 Keypad Operation Overview STEP 2 Standard Wiring Diagrams and Connections STEP 3 Start Up Wizard STEP 4 Operating and Programming Menu Navigation STEP 5 Faults and Warning Indi...

Page 2: ...active drive alarm s Fault Indicates that there is one or more active drive fault s I O Terminal Indicates that the I O terminals have been chosen for control Keypad Indicates that the keypad has bee...

Page 3: ...ss disabled by the StopButtonActive parameter used to reset the active faults Reset Resets the active faults Local Remote Switches between LOCAL and REMOTE control for start speed reference and revers...

Page 4: ...e parameters See the SVX9000 Application Manual for identification of these parameters specific to your chosen application Main Menu The data on the control keypad are arranged in menus and submenus T...

Page 5: ...otor Wiring for Large Horsepower Drives 20 250 hp U V W B M 3 L1 L2 L3 L1 L2 L3 B R External RFI Filter Optional BR Optional External Filter Optional BR Power Board 230V 20 30 hp 480V 40 250 hp Contro...

Page 6: ...s etc max 0 1A 7 GND I O ground Ground for reference and controls 8 DIN1 Start forward Contact closed start forward 9 DIN2 Start reverse Contact closed start reverse 10 DIN3 External fault input progr...

Page 7: ...Min Freq 0 00 Hz Max Freq 60 00 Hz Accel Time 3 0 s Decel Time 1 3 0 s Current Limit 3 30 A Motor NP Volt 460 V Motor NP Freq 60 00 Hz Motor NP Speed 1720 rpm Motor NP Current 2 20 A Power Factor 0 8...

Page 8: ...M3 Motor Voltage 255 7 V O7 DC Bus Volt 580 V O8 Unit Temp 32 C O9 Motor Temp 0 1 O10 M5 Programming Press Enter M6 M7 Operate Mode Press Enter M8 Operate Menu Programming System Menu S1 S8 Expander B...

Page 9: ...nds While in the other menus if there is no keypad activity the display will return to the Operate Menu after 30 seconds Code Signal Name Unit Description O 1 Output Frequency Hz Output frequency O 2...

Page 10: ...eplate value P1 11 Start function 0 1 0 505 0 Ramp 1 Flying start P1 12 Stop function 0 3 1 506 0 Coasting 1 Ramp 2 Ramp Run enable coast 3 Coast Run enable ramp P1 13 Local Control Place 1 3 2 171 1...

Page 11: ...frequency that corresponds to the max reference signal 0 00 No scaling P1 2 6 Reference inversion 0 1 0 305 0 Not inverted 1 Inverted P1 2 7 Reference filter time 0 00 10 00 s 0 10 306 0 00 No filter...

Page 12: ...signal selection AnOUT 0 1 AnOUT E 10 AnOUT 0 1 471 TTF programming method used P1 3 13 Analog output 2 function 0 8 4 472 See P1 3 2 P1 3 14 Analog output 2 filter time 0 00 10 00 s 1 00 473 0 00 No...

Page 13: ...normal ramp time Code Parameter Min Max Unit Default Cust ID Note P1 6 1 Motor control mode 0 1 0 600 0 Frequency control 1 Speed control P1 6 2 V Hz optimization 0 1 0 109 0 Not used 1 Automatic torq...

Page 14: ...See P1 7 3 P1 7 14 Stall current 0 1 InMotor x 2 A IL 710 P1 7 15 Stall time limit 1 00 120 00 s 15 00 711 P1 7 16 Stall frequency limit 1 0 P1 1 2 Hz 25 0 712 P1 7 17 Underload protection 0 3 0 713...

Page 15: ...Fault Fault Code Fault 1 Overcurrent 16 Motor overtemperature 40 Device unknown 2 Overvoltage 17 Motor underload 41 IGBT temperature 3 Ground Earth Fault 22 EEPROM checksum fault 42 Brake resistor ove...

Page 16: ...fied and then the up or down arrow keys to select the new item Press the ENTER key to accept the change Code Signal Name Unit Description V7 1 Output Frequency Hz Output frequency V7 2 Frequency refer...

Reviews: