SVS/12
994.530 G01 02
17
2.2 Description of panel types 630 A
2.2.1
Circuit-breaker panel
A circuit-breaker panel includes the following principal
components as standard:
a busbar system
a disconnector
a circuit-breaker
one of four connection possibilities:
three plug-in connection cones (24 kV) for one
cable per phase (figure 1)
three plug-in connection cones (24 kV) for two
cables per phase (figure 2)
a terminal block with locked cable entry ports for
Eaton Magnefix cable boxes (12 kV) (figure 3)
three terminal blocks for cable socket connection
(12 kV) for one cable per phase, see chapter 2.3.1,
figure 3.
an operating mechanism
a control panel
Options
The following options are available as standard:
auxiliary contacts for circuit-breaker and disconnector
electrical opening and closing of the circuit-breaker
cable side voltage transformers
cable side overvoltage deflectors
secondary instrument compartment
current transformers, secondary equipment
Applications of standard version
Incoming and outgoing supply panels
Generator panels
Motor panels
Transformer panels
SPECIAL VERSION
Circuit-breaker with integrated protection No separate
auxiliary voltage is needed, since the current
transformers supply the power for opening.
Applications of special version
Protected transformer panel or cable panel in stations
without auxiliary voltage.
Operat ing
mechanism
Cont rol
panel
Circuit -
breaker
Disconnect or
Busbar syst em
Connect ion cone
1.
2.
3.
Summary of Contents for SVS/12
Page 133: ...SVS 12 994 530 G01 02 133 9 2 Voltage detecting system Wega 1 2...
Page 134: ...SVS 12 134 994 530 G01 02...
Page 135: ...SVS 12 994 530 G01 02 135...
Page 136: ...SVS 12 136 994 530 G01 02...
Page 137: ...SVS 12 994 530 G01 02 137 9 3 Phase monitor Orion 3 0...
Page 138: ...SVS 12 138 994 530 G01 02...