IB505040EN
UX AC only Exit Sign Installation Instructions
www.eaton.com/lighting
Figure 1
INSERT
SCREWDRIVER
HERE TO
REMOVE STENCIL
INSERT
SCREWDRIVER
HERE TO
REMOVE
STENCIL
2
Figure 2
SLOT
TAB
SLIDE SLOTS OVER TABS TO
TEMPORARILY HANG
FIXTURE FOR WIRING
Figure 3
WIRE
CONNECTIONS
ALLOWED IN
ENCLOSURE
AREAS
NO WIRE CONNECTIONS
ALLOWED IN SIGN FACE
WIRE
CONNECTIONS
ALLOWED IN
ENCLOSURE
AREAS
Figure 4
KNOCKOUT
(REMOVE
AS NEEDED)
WATER TIGHT
CONDUIT HUB
CONDUIT
HUB NUT
7. Connect power supply and ground in accordance with local
codes. Wire connections as follows: 277VAC line to Orange
lead or 120V line to Black lead; Neutral to white lead. Ground
to Green Screw on backplate (single face), frame (double
face) or conduit hub with integral terminal, if provided. Cap
unused line lead with wire nut provided (see Schematic).
Connections must be in the enclosure rated area of the
frame (See Figure 3), not in the sign face. Make sure wires
are routed so they do not create shadows on the face of the
exit.
8. Determine which color sign face is needed. If red is needed,
proceed to step 11.
9. If green is the desired color, remove the red lens from the
stencil by removing the white vinyl caps holding the lens in
place and replace it with the green lens provided. Replace
the white vinyl caps.
10. On the LED circuit board, locate the red/green jumper (See
Schematic).The jumper should be in the red position per the
silk screen printing on the board. Pull gently upward on the
jumper, then shift it one pin over to activate the green LEDS.
11. Replace the stencil cover assembly, and weather shield. To
insure a water tight fit, make sure the gasket and weather
shield edge are clean and free of debris.
12.Energize AC supply, LED display will come on.
NOTE:
The foam gasket is suitable for smooth surfaces, but
for rough surface mounting, silicone caulk should be used to
prevent water from entering the exit sign.