The Configuration screen (
) is setup by Eaton PDI at the factory and requires Eaton PDI authorization
to make changes, but any user can view the screen. Touch the Config button to view.
Eaton PDI uses the Configuration screen to describe the system to the Monitor software, which is common for
all Eaton PDI STS products. Parameters include physical characteristics (standalone or redundant system,
contractor board installation, fans, number of isolation MCSWs), power (voltages, frequency, KVA, etc.), and
distribution options.
Figure 21. Configuration Screen
1100..22
S
Sw
wiittcchh S
Seettttiinnggss S
Sccrreeeenn
Touch the
Switch button
in the navigation buttons to display the
Switch Settings
screen (
). The
Switch Settings
screen is used to select or adjust parameters for sense and transfer algorithms.
Two of the three main transfer parameters—transfer algorithm and re-transfer setting—are set on the
Switch
Settings
screen and require administrator or other higher level authorization. The remaining choice—Preferred
Source—is set on the Home screen and requires operator-level authorization.
Use the
Controls
panel to select the transfer algorithm and retransfer behavior by setting these virtual
switches:
•
Mode (VSS/POG):
When the
VSS/POG
switch is touched to be moved, the
Execute
button is
highlighted as a precaution. The operator must touch
Execute
to move the virtual switch to the opposite
position, or
Cancel
to revert back to the previous selection. (See also