22
System Parallel Module
Chapter 7 Product Specifications
The following sections detail the SPM specifications and the environmental and safety specifications for the
SPM. Environmental and Safety Specifications.
This section provides the following specifications:
•
Model Numbers
•
Environmental and safety specifications
7 .1
Specifications
Basic Unit rating
Units
rating 50/60hz
kVA
120kVA x 3
200kVA x 3
Input and output voltage
Volts
415
415
Max. current of MBS
Amps
705
1173
Max. current of MIS
Amps
654
1086
Max. current of MOB
Amps
218
362
operating Temperature
①
5°C – 40°C
Storage Temperature
①
-25°C to 55°C
Transit Temperature
①
-25°C to 60°C
humidity
5 % to 95 % maximum noncondensing
Enclosure Class per IEC 60529
IP20, Optional 21
rohS/WEEE
Required
operating
Altitude
②
Maximum 1000m at 30°C without derating
①
The recommended operational, storage and transit temperature with CSB and C&D batteries is
generally max. 25°C. Please refer to the battery manufacturer’s recommendations for accurate
temperatures.
②
Altitude-thermal de-rating as per EN62040-3:2011.
7 .1 .2 Environmental
specifications
7 .1 .1 Electrical
specifications
Summary of Contents for SPM 120
Page 1: ...System Parallel Module Installation and Operation Manual Eaton UPS Accessories...
Page 2: ......
Page 25: ...19 System Parallel Module Notes...
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ...614 01728 00...