Sonix Hmi-5 Technical Manual
20
SONIX HMI-5 TECHNICAL MANUAL
TM373 / A June 2022 www.eaton.com
8 Programming units
The Hmi-5 access panels are controlled by a Microsemi
ProASIC3 FPGA with instant-on technology for fast and
reliable operation.
Required equipment for programming units:
•
Computer/laptop with Microsemi FlashPro 11.x
installed
•
Microsemi Flash Pro 4 or newer programmer
•
Connection cable for programmer to unit (2x5 0.1”
pitch)
•
Eaton firmware for target unit – Verify firmware is for
correct unit
•
Power source for Hmi-5 access panel, must be
powered via Hmi-Barrier
Warning:
Unit MUST be powered via Hmi-
Barrier or certification will be voided and there is
potential for damage to the unit
Procedure for programming units is as follows:
1. Visual inspection of unit to ensure no damage to PCB
and components
2. Connect power to A side of unit using either:
a. 24 V dc phantom power via Hmi-Barrier into J1 (Audio (+ve)
and screen (-ve))
3. Connect Microsemi programmer to J4
a. Observe orientation of notch
4. Open FlashPro software on laptop and load firmware
file
a. See FlashPro documentation for details
5. Program unit firmware
6. Verify unit firmware
7. Power cycle Hmi-5 A Side
8. Using SAS:
a. Check / Set Unit ID
b. Check / Set Configuration
9. Verify operation
a. Alarms
b. Speech broadcasts
10.Repeat for B side of Hmi-5
a. DC input is into J5 (Phantom)
b. Programming connector is J8
Warning:
Programming firmware is potentially
damaging to the unit if not performed correctly
with Eaton tested and approved firmware.