Commissioning
104
02/11 MN05006002Z-EN
Remedy:
With the aid of the status LED ascertain which of the Smart-
Wire-DT slaves is no longer being found by the SmartWire-
DT gateway. Then check where there is a possible damage
to the SmartWire-DT cable or an SEL link is missing.
Switching on in the case of a changed project config-
uration
Basic requirements:
• Target configuration = Actual configuration,
• A connection to the field bus master is available.
If, after the switch-on and initialisation process, the Smart-
Wire-DT gateway ascertains a difference between the stored
target configuration and the project configuration, it indi-
cates this error with the following LED combination.
Table 15:
LED indication of the SmartWire-DT gateway in the
case of a project configuration deviation
Remedy in case of a changed project configuration:
X
Retrace the change on the SmartWire-DT network.
X
Interrupt the connection to the field bus master by pulling
out the field bus plug.
X
Press the
“Config.” pushbutton actuator
for at least
2 seconds.
The SmartWire-DT gateway stores the changed actual
configuration as a new target configuration
h
If an SmartWire-DT slave is no longer connected, the SWD
LED is switched off.
LED
Status
SWD
Green continuous light
Config.
Red continuous light