Eaton SmartRack SRP-R-C25 Owner'S Manual Download Page 1

1

Owner’s Manual

PRODUCT REGISTRATION

Register your product today for a  

chance to win an ISOBAR

®

 surge  

protector in our monthly drawing!

Tripplite.Eaton.com/warranty

Este manual está disponible en español en la página de Eaton:  

Eaton.com/support
Ce manuel est disponible en français sur le site Web de Eaton :  

Eaton.com/support

Purchased product  

may differ from image.

SmartRack

®

 Modular Data Centers

Summary of Contents for SmartRack SRP-R-C25

Page 1: ...surge protector in our monthly drawing Tripplite Eaton com warranty Este manual est disponible en espa ol en la p gina de Eaton Eaton com support Ce manuel est disponible en fran ais sur le site Web d...

Page 2: ...ructions 3 Overview 6 Configuration 7 Installation 15 Appendix 21 Individual Enclosure Submittal Drawings 21 Complete Configuration Submittal Drawings 24 InRow Cooling Submittal Drawings 37 Technical...

Page 3: ...n or instruction concerning use of the appliance by person responsible for their safety Children should be supervised to ensure that they do not play with the appliance This appliance is classified as...

Page 4: ...uide and Installation Manual 1 3 IT Rack Enclosure and Service Enclosure Warnings Keep the enclosures in a controlled indoor environment away from moisture temperature extremes flammable liquids and g...

Page 5: ...A rolling enclosure can cause personal injury and property damage if not properly supervised If rolling the enclosure down a ramp is required use extreme caution Do not attempt to use ramps that have...

Page 6: ...nitoring equipment Locking doors and panels help keep contents secure TanLock door access security options including pin fingerprint keypad and RFID are also available Power and data cables can be sep...

Page 7: ...p securing the corner protectors Apply the utility blade directly over the corner protectors to prevent the utility blade from scratching the enclosure or cutting the heavy protective plastic bag bene...

Page 8: ...s are present If anything is missing or damaged contact Eaton for assistance Do not attempt to use the enclosure if it has been damaged 3 3 4 Use a 13 mm open end wrench to remove the shipping bracket...

Page 9: ...at the rear of the enclosure Slowly push the enclosure toward the back of the shipping pallet until all four casters go over the edge of the pallet and touch the floor WARNING Use at least one assista...

Page 10: ...Do not attempt to roll the enclosures over long distances The enclosures should be moved close to their installation location before they are unpacked use a forklift or pallet jack if necessary WARNIN...

Page 11: ...cooling enclosure as needed and have a local certified HVAC professional connect the cooling unit to the outdoor condenser and power connections to the cooling unit Please follow the cooling unit ins...

Page 12: ...crylic Window 5 Adjustable Cable Service Hood with 4 Cable Entry Hole Options 6 Customizable Service Enclosure with Vented Door 7 Cable Management Plenum 8 Locking Removable Side Panels 9 Locking Hand...

Page 13: ...een moved to the installation location ensure the entire unit is level for proper condensate drainage Use a carpenter s level to check the slope of the floor If the floor slopes more than 1 choose an...

Page 14: ...hardware used to secure the enclosures to the shipping pallets Use a 13 mm open end wrench to connect the brackets to each enclosure s outer bracket mounting points Then attach the brackets to secure...

Page 15: ...on Manual 4 2 IT Enclosure Installation 4 2 1 IT Enclosure Roof Panel The IT Enclosure s roof panel is adjustable 4 Installation 1 Determine the cable routing hole s where the cable hood s will be pos...

Page 16: ...T Rack enclosure from the top Route the cable s from the IT Enclosure through the brush strips into the cable plenums on the top of the enclosure and out through the cable hood Option 2 Raised Floor I...

Page 17: ...ures 1 Remove the top horizontal beams of the enclosures you wish to run wire through 2 Run the cable s through the brush strips and across to the neighboring racks 3 Optional Depending on the cable m...

Page 18: ...ly in inch 6 mm increments 1 Each rail is connected to the enclosure with 6 screws 1 pair at the upper beam 1 1 pair at the middle beam 2 and 1 pair at the lower beam 3 4 5 6 3 4 5 6 7 8 9 0 1 2 3 4 5...

Page 19: ...ides of the square opening in the rail not the top and bottom Follow the instructions in your equipment documentation to ensure proper installation of your equipment Installing Cage Nuts 1 Locate the...

Page 20: ...Place the cup washers between the screws and the equipment mounting brackets Note Your equipment may also include mounting hardware Read the mounting instructions that came with your equipment before...

Page 21: ...K VIEW TOP VIEW SIDE VIEW TOP VIEW DOORS OPEN 23 62 600 23 62 600 6 41 162 90 2 91 74 22 62 574 61 90 90 34 64 879 75 34 64 879 75 4 15 105 40 12 24 311 9 35 237 50 8 33 211 50 8 33 211 50 12 80 325 6...

Page 22: ...W TOP VIEW TOP VIEW DOORS OPEN SIDE VIEW 16 54 420 5 12 130 34 64 879 75 65 65 1667 50 86 13 2187 70 93 80 2382 50 34 64 879 75 2 15 54 53 3 33 84 60 16 54 420 8 33 211 50 8 33 211 50 40 41 1026 50 DI...

Page 23: ...NT VIEW SIDE VIEW BACK VIEW TOP VIEW SIDE VIEW TOP VIEW DOORS OPEN 31 61 803 31 61 803 14 65 372 90 90 90 90 34 64 879 75 34 64 879 75 62 17 1579 8 33 211 50 8 33 211 50 15 35 390 15 35 390 40 41 1026...

Page 24: ...0 Eaton Boulevard Cleveland OH 44122 United States Eaton com 2024 Eaton All Rights Reserved Publication No 23 11 116 40 56 1030 20 40 56 1030 20 66 23 1682 25 95 38 2422 62 64 69 1643 2 86 72 52 COOLI...

Page 25: ...e properties of their Eaton 1000 Eaton Boulevard Cleveland OH 44122 United States Eaton com 2024 Eaton All Rights Reserved Publication No 23 11 117 40 56 1030 20 40 56 1030 20 66 23 1682 25 95 38 2422...

Page 26: ...ton Boulevard Cleveland OH 44122 United States Eaton com 2024 Eaton All Rights Reserved Publication No 23 11 118 March 2024 6 64 25 1632 64 25 1632 66 23 1682 25 95 38 2422 62 64 69 1643 2 86 72 52 CO...

Page 27: ...ton Boulevard Cleveland OH 44122 United States Eaton com 2024 Eaton All Rights Reserved Publication No 23 11 119 March 2024 6 64 25 1632 64 25 1632 66 23 1682 25 95 38 2422 62 64 69 1643 2 86 72 52 CO...

Page 28: ...8 20 81 43 2068 20 66 23 1682 25 95 38 2422 62 64 69 1643 2 86 72 52 COOLING SYSTEM FRONT VIEW SIDE VIEW BACK VIEW TOP VIEW 16 54 420 23 62 600 6 41 162 90 5 12 130 2 91 74 34 64 879 75 34 64 879 75 2...

Page 29: ...62 64 69 1643 2 86 72 52 COOLING SYSTEM FRONT VIEW SIDE VIEW BACK VIEW TOP VIEW 16 54 420 23 62 600 6 41 162 90 5 12 130 2 91 74 34 64 879 75 34 64 879 75 2 15 54 53 3 33 84 60 4 15 105 40 9 35 237 5...

Page 30: ...nited States Eaton com 2024 Eaton All Rights Reserved 112 90 2867 70 112 90 2867 70 66 23 1682 25 95 38 2422 62 64 69 1643 2 86 72 52 COOLING SYSTEM FRONT VIEW SIDE VIEW BACK VIEW TOP VIEW 16 54 420 2...

Page 31: ...aton All Rights Reserved Publication No 23 11 123 March 2024 129 50 3290 129 50 3290 66 23 1682 25 95 38 2422 62 64 69 1643 2 86 72 52 COOLING SYSTEM FRONT VIEW SIDE VIEW BACK VIEW TOP VIEW 16 54 420...

Page 32: ...com 105 04 2668 105 04 2668 66 23 1682 25 95 38 2422 62 64 69 1643 2 86 72 52 COOLING SYSTEM FRONT VIEW SIDE VIEW BACK VIEW TOP VIEW 16 54 420 23 62 600 6 41 162 90 5 12 130 2 91 74 34 64 879 75 34 64...

Page 33: ...com 2024 Eaton All Rights Reserved Publication No 23 11 125 March 2024 7 136 75 3473 50 136 75 3473 50 66 23 1682 25 95 38 2422 62 64 69 1643 2 86 72 52 COOLING SYSTEM FRONT VIEW SIDE VIEW BACK VIEW T...

Page 34: ...91 74 34 64 879 75 34 64 879 75 2 15 54 53 3 33 84 60 4 15 105 40 9 35 237 50 8 33 211 50 8 33 211 50 12 80 325 64 69 1643 12 80 325 64 69 1643 12 80 325 64 69 1643 12 80 325 64 69 1643 12 80 325 64 6...

Page 35: ...tates Eaton com 2024 Eaton All Rights Reserved Publication No 23 11 127 March 2024 6 128 90 3274 128 90 3274 66 23 1682 25 95 38 2422 62 64 69 1643 2 86 72 52 COOLING SYSTEM FRONT VIEW BACK VIEW TOP V...

Page 36: ...K VIEW TOP VIEW 16 54 420 23 62 600 6 41 162 90 5 12 130 2 91 74 34 64 879 75 34 64 879 75 2 15 54 53 3 33 84 60 4 15 105 40 9 35 237 50 8 33 211 50 8 33 211 50 12 80 325 64 69 1643 12 80 325 64 69 16...

Page 37: ...Input F Gas Pipe G Liquid Pipe H Accessory and Network Cable Access Port I Water Drainpipe Robust cooling in a space saving footprint for your data center IT room or other edge location Up to 88 000 B...

Page 38: ...Height 2000 mm 78 7 in 42U 2000 mm 78 7 in 42U Unit Depth 1100 mm 43 3 in 1100 mm 43 3 in Unit Width 300 mm 11 8 in 300 mm 11 8 in Unit Weight 180 kg 397 lb 198 kg 437 lb Unit Carton Weight 215 kg 474...

Page 39: ...39 Appendix 3 Dimensions mm inches 1103 43 43 131 5 16 232 9 13 50 1 97 300 11 81 1127 44 37 170 6 69 300 11 81 1544 60 79 2000 78 74 Models SRCOOLDXRW12 SRCOOLDXRW25...

Page 40: ...40 Appendix 4 Dimensions mm inches 425 1 16 74 280 11 02 800 31 50 1239 48 78 339 5 13 4 550 21 7 Outdoor unit for SRCOOLDXRW12 Models SRCOOLDXRW12 SRCOOLDXRW25...

Page 41: ...DXRW12 SRCOOLDXRW25 654 25 75 298 11 73 1276 50 24 150 5 91 150 5 91 452 17 80 907 35 71 1175 46 26 1407 55 39 997 39 25 501 19 72 1407 55 39 1126 44 33 1232 48 50 997 39 25 121 4 76 943 37 12 837 32...

Page 42: ...42 Appendix 6 Dimensions mm inches Front Clearance 1000 40 Rear Clearance 1200 48 Models SRCOOLDXRW12 SRCOOLDXRW25 Clearance Requirements Indoor Units...

Page 43: ...ix 7 Dimensions mm inches 1019 40 788 31 798 31 5 498 19 5 1023 41 5 1240 49 3000 118 500 19 7 800 31 5 500 19 7 Models SRCOOLDXRW12 SRCOOLDXRW25 Clearance Requirements Outdoor Units SRCOOLDXRW12 SRCO...

Page 44: ...Samdy Dallen Colin Dallen A L1 N PE Main L3 L2 L1 PE 0 Y Condenser Power Condenser Signal L2 L1 Heater Power for Low Temp L2 L1 Solenoid Power for Low Temp Webcard Modbus TCP L2 L1 Solenoid Power for...

Page 45: ...me in backup power and power management The acquisition of Tripp Lite transforms Eaton s distributed IT infrastructure and connectivity equipment capabilities Combining our product strengths and exper...

Page 46: ...Color touchscreen user interface Air filtration R 410A refrigerant Outdoor air cooled condenser Electronic expansion valve Top bottom piping and electrical connections Onboard logic controller High se...

Page 47: ...cceptable humidity operating range indoor 5 to 80 RH 5 to 80 RH Maximum operational altitude see chart in Section DD for altitude correction factors up to 13 000 ft 4 000 m up to 13 000 ft 4 000 m For...

Page 48: ...OR FANS 1 Qty 3 fans SRCOOLDXRW12 Qty 6 fans SRCOOLDXRW25 2 EC variable speed adjusts automatically according to heat load to meet the user specified setpoint 3 Airflow a SRCOOLDXRW12 1233 CFM 2543 RP...

Page 49: ...g capacity as well as the compressor heat a SRCOOLDXRW12 18kW b SRCOOLDXRW25 38kW SRCOOLDXRW12 SRCOOLDXRW25 Condenser Maximum total heat rejection condenser 18 kW 38 kW Discharge fitting size 5 8 in 7...

Page 50: ...tical piping diameter Varies see installation manual Liquid line piping diameter Varies see installation manual Copper pipe type ACR Type L hard drawn preferred S trap vertical discharge piping Every...

Page 51: ...IONS 1 Top or bottom entry piping electrical can be routed from top or bottom into the In Row cooler no modifications required 2 Designated ports both top and bottom with grommets to protect against v...

Page 52: ...ty sensor failure 2 Return air temperature high 3 Return air temperature low 4 Return air temperature sensor failure 5 Suction pressure low 6 Suction pressure sensor failure 7 Suction temperature sens...

Page 53: ...ture delta 7 Draw thru design allows fans to pull air evenly across coil rather than forcing air past that can lead to leaks and inefficiency 8 Condensate drain pan affixed directly below the cooling...

Page 54: ...ply air temperature sensor along with other sensors to control system behavior 4 Firmware upgradeable in field X FILTERS 1 Qty 2 extending full height of cabinet 2 Efficiency rating G4 3 Replaceable a...

Page 55: ...B 29 RH 66 56 F 19 2 C WB 11 8 kW 11 8 kW 23 4 kW 24 2 kW 86 F 30 C DB 34 RH 65 84 F 18 8 C WB 10 9 kW 11 7 kW 21 6 kW 23 9 kW 82 4 F 28 C DB 45 RH 67 1 F 19 5 C WB 9 4 kW 11 9 kW 18 4 kW 24 3 kW 82 4...

Page 56: ...air humidity low Return air humidity sensor failure Return air temperature high Return air temperature low Return air temperature sensor failure Suction pressure low Suction pressure sensor failure S...