Chapter 4: Handling, storage, and installation
SC9000 EP medium voltage drives
IB020001EN—February 2016
www.eaton.com
11
Table 6. 4160 V AFD typical shipping section weights (lb)
Frame
hp
Shipping sections
Converter
Total
Transformer
Inverter
Main disconnect
Incoming
A
300
5825
—
—
—
—
5825
350
5925
—
—
—
—
5925
400
6025
—
—
—
—
6025
450
6225
—
—
—
—
6225
500
6225
—
—
—
—
6225
600
6525
—
—
—
—
6525
700
6825
—
—
—
—
6825
800
7175
—
—
—
—
7175
900
7625
—
—
—
—
7625
B
1000
6985
1940
—
—
—
8925
1250
7435
1940
—
—
—
9375
1500
8085
2040
—
—
—
10,125
1750
8585
2040
—
—
—
10,625
2000
9585
2340
—
—
—
12,025
C
2250
10,185
2540
1300
—
—
14,025
2500
11,185
2540
1300
—
—
15,025
D
3000
12,685
3040
1850
1300
—
18,325
3500
13,135
3740
1850
1300
—
19,575
4000
13,685
3840
1850
1300
—
20,125
4500
14,185
4040
1850
1300
—
20,825
5000
14,685
4140
1850
1300
—
21,425
E
4750–6000
18,300
4800
1850
1300
1300
27,550