System Operation
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
89
Digital Inputs
The Input / Output (I/O) board is fitted with a number of configurable digital inputs (DI) which
can monitor external voltage-free relay contacts or switches. See Input / Output Board on page 3
for details.
► To configure a digital input
1
On DCTools/web, go to
Digital Inputs
. Expand the
Digital Inputs
table.
The number of digital inputs available for user digital inputs depends on the IO Board version.
Refer to the I/O Board (IOBGP-xx) Connector Pin-outs on page 138 for IO Board input numbers.
If additional I/O boards and/or SiteSure-3G modules are connected, there will be more
configurable Digital Inputs. See details in the dc power system Installation and Operation Guide.
Some digital inputs are normally configured as Digital System States (see details on page 88).
Only use these inputs if you do need need to use them as Digital System State Inputs.
2
Select a configurable Digital Input.
3
Configure the following parameters to suit the application.
To change a setting, double-click and select from drop down list or edit the text.
Parameter
Setting
Status
Set to
Enabled
.
Name
Type the name of the input.
Function
Set to
User Defined
.
IOB Number
The number of the I/O board (or SiteSure-3G module if connected). Do not
change.
IOB DI Number
The number of the DI on the I/O board (or SiteSure-3G module if connected).
Do not change.
Active State
Select the state of the input that will activate the DI.
Group
Set to 0 unless using Groups in PowerManagerII. See PowerManagerII online
help for details.