Instruction Leaflet
IL29C150G
Effective December 2011
Installation Instructions for Shunt Trip for
R-Frame Series C Circuit Breakers and
Molded Case Switches
EATON CORPORATION
www.eaton.com
TABLE 1-1. SHUNT TRIP ELECTRICAL RATINGS DATA
Average circuit breaker contact total opening time approximately
62
milliseconds, at rated voltage
Endurance
-
500
electrical operations.
Shunt trip can be operated up to a maximum of
six times per minute.
Maximum operating voltage - 110% of maximum voltage range rating.
Catalog
Ratings
Electrical
Ratings
One Minute
Dielectric
0.250s
0.033s
Withstand
Notes
(1) Suitable for use with Class 1
GFP devices; marking label supplied with accessory kit.