Eaton PXL Series Installation And Operation Manual Download Page 3

Section 1 Introduction

Instruction Manual

Page 3 Effective: January 2006

PXL Series Installation
and Operation Manual

The PXL series of Surge Protective
Devices (referred to as PXL from this
point forward) offer surge protection and
filtering to provide clean power for
sensitive electronic loads. The PXL units
shunt high energy induced lightning
surges, as well as other formats of
transient disturbances. Properly installed
PXL units protect critical equipment in
hospital, commercial, computer
manufacturing, telecommunication,
financial and military facilities.

The PXL removes power disturbances
from electrical distribution systems using
a low impedance shunt path to ground.
Surges and electrical line noise are
absorbed by the PXL and are prevented
from traveling through distribution system
wires to sensitive electronic loads. Prior to
installing the PXL check the units voltage
and configuration to verify it matches your
system voltage and wiring configuration.

Section 2

Section 3

of this manual details the

installation procedures for the PXL
Series SPDs.

of this manual describes

the operating features for the PXL
Series SPDs.

Section 4

Note:

of this manual provides a

detailed troubleshooting guide.

Surge Protective Devices and

Hi-Potential (Hi-Pot) Testing.

It is common procedure to test distribution
equipment with a form of hi-pot (dielectric
or megger) testing. The hi-pot tester
outputs a high voltage signal at low
current that will shut down if a short
circuits occurs. The principle behind hi-
pot testing is that the high voltage will find
any faults in the distribution system and
then quickly shuts down without
damaging the distribution equipment.
Hi pot testing is usually conducted phase
to phase and phase to ground.

1.1 Surge Protective Device

A Surge Protective Device (SPD) acts
very quickly to suppress high voltages
before they can damage sensitive
electronics. An SPD normally acts in the
nanoseconds range and can withstand
tens of thousands of amps repeatedly.
SPDs are not designed to prevent a
continued overvoltage without damaged.
In order to protect electronics from
damage, an SPD must be connected
from phase to ground. Lightning surges
are almost always shunted to ground and
the SPD must be connected this way to
provide protection.

1.2 The Problem

1.3 Disconnecting SPDs/
Performing Hi-Pot Testing

During a hi-pot test, the SPD will turn on
and shunt the high voltage to ground. The
hi-pot tester will continue to supply
current until it internally records the fault
condition. By this time, the SPD has been
exposed to a continues current that can
damage the internal components. To
prevent damage, it is critical that hi-pot
testing not be performed on connected
SPDs. From the installers point of view, it
is also important that SPDs are not
connected while performing a hi-pot test
since the SPD will always cause the test
to fail, thus defeating the purpose of the
test.

The only way to perform a hi-pot test in
the presence of an SPD is to disconnect
the SPD from the distribution system. If
the unit is connected through circuit
breaker, the breaker should be shut off as
a first step. This is sufficient for a delta
system to remove the SPD. On Wye
connected systems, the neutral must also
be removed so that all paths to ground
are isolated. An alternative method is to
remove the ground from the SPD before
any hi-pot testing is performed. All
grounds must be removed: the wired
ground, the conduit ground and the case

ground. Because it is easy to miss a
ground connection, it is recommended
that the line and neutral connection are
removed rather than the ground
connection.

Eaton Electrical tests each device and
assembly separately for dielectric
breakdown. The assembled SPD has
already been tested at the factory.
Additional tests should not be required.
Due to the possible damage that can
occur, all SPDs have a caution label
applied warning against hi-pot testing of
the assembly. We recommend that hi-pot
testing not be done on distribution
equipment with PXL SPD already
mounted. If hi-pot testing is still going to
be done, it can be accomplished by
following the above instruction and
removing the phases and neutral
connections from the SPD. If all wires to
these terminals are removed, a hi-pot
test can be safely performed. It is very
important to reconnect all wires after the
test. If any wire is left off, it can constitute
a serious hazard or can defeat the
operation of the SPD rendering it non-
functionial.

Verify your system application voltage
and wiring configuration is the same as
the enclosed PXL by checking the
voltage rating label located on the PXL
enclosure.
Review the site to ensure the physical
space required to install the PXL exists.
Check the facility grounding system. All
grounding, bonding and earthing must
meet NEC or CEC, as well as any other
applicable national or local codes. A poor
ground or grounding/bonding violations
affect the suppressor’s ability to function
as specified.

1.3.1 Eaton Electrical Specific
Instruction

Section 2 Installation
Procedures

2.1 Site Preparation

WARNING

INSTALLING A PROTECTION DEVICE

WHICH IS UNDER-RATED FOR THE

ELECTRICAL SYSTEM VOLTAGE

CAN CREATE A POTENTIALLY

HAZARDOUS CONDITION

CAUTION

CONDUCTING DIELECTRIC OR HI-

POTENTIAL TESTING WILL CAUSE

INTERNAL DAMAGE TO SPD UNIT.

DO NOT PERFORM DIELECTRIC OR

HI-POTENTIAL TESTING WITH THE

SPD INSTALLED.

CAUTION

PXL TO BE INSTALLED OR

REPLACED BY A QUALIFIED

ELECTRICIAN

IM 01005001E

information visit: www.eatonelectrical.com

Effective 01.06

Summary of Contents for PXL Series

Page 1: ...Installation and Operation Manual for Powerware PXL Series Surge Protective Device IM 01005001E For more information visit www eatonelectrical com Effective 01 06 Instruction Manual IM01005001E...

Page 2: ...Table of contents Description Page Section 1 Introduction 3 Section 2 Installation Procedure 3 Section 3 Operating Features 6 Section 4 Troubleshooting 7 Section 5 Warranty and Technical Assistance 15...

Page 3: ...at hi pot testing not be performed on connected SPDs From the installers point of view it is also important that SPDs are not connected while performing a hi pot test since the SPD will always cause t...

Page 4: ...e Twist and bind together all leads Route the wires such that their overall length is kept to a minimum This reduces line impedance and optimizes performance Strip the ends of the wires and terminate...

Page 5: ...ge 5 Effective January 2006 SPD Figure 3 3 Phase Wye 4 Wire Ground PE Voltage Codes 208Y 480Y CPS Figure 2 3 Phase Delta 3 Wire Ground PE Voltage Codes 240D 480D SPD Figure 1 Single Phase Split Phase...

Page 6: ...perating status each PXL is equipped with status indicator lights All units are equipped with integral fusing Should the SPD fail and create a short circuit the overcurrent will isolate the fault Thes...

Page 7: ...form C relay monitoring contacts by switching the power and back Contact are rated up to 1A 220 VAC NO NC COM OFF ON Note Section 4 Troubleshooting 4 1 Life expectancy Note The PXL is not field repai...

Page 8: ...e surges should not be confused with voltage regulation problems By definition voltage surges occur in the microsecond range and voltage regulation is defined as having a duration of 1 cycle to many c...

Page 9: ...m All LEDs are green No alarms Normal operation 3 phase configuration NA Two green LEDs are ON Split phase configuration Normal operation NA 100KA All green LEDs are ON Alarm disabled LED ON Normal op...

Page 10: ...and N G voltage should be less than 3 volts for 3 phase 4 wire system Lost Neutral Condition 2 Neutral conductor not connected or poor connection intermittent All LEDs are OFF buzzer OFF One or more r...

Page 11: ...formation on the Premium display menu features All LEDs are green No alarms Normal operation 3 phase configuration NA VAN VBN 120 120 Two LEDs are green No alarms Normal operation split phase configur...

Page 12: ...VAC VCA 208 81 208 Lost phase voltage No voltage on specified phase Confirm corresponding SPD phase connection terminals are connected Check breaker voltage Check panel voltage One or more red LEDs ON...

Page 13: ...08 208 208 Internal fuse blown Measure terminal voltage with multimeter and if voltage is in spec then call Press DISABLE ALARM button on display United States support 1 800 809 2772 Australia support...

Page 14: ...5 2 Premium Display Calibration Procedure Steps Shut OFF power to the unit Press and hold the STEP button Do NOT release arrow 2 Apply power to the unit The display will show first row second row Rel...

Page 15: ...Y AS TO THE MERCHANT ABILITY FITNESS FOR PURPOSE SOLD DESCRIPTION QUALITY PRODUCTIVENESS OR ANY OTHER MATTER In no event shall Eaton Powerware be liable for special or consequential damages or for del...

Page 16: ...2006 Eaton Corporation All Rights Reserved Printed in USA Publication No IM01005001E 1000 Cherrington Parkway Moon Township PA 15108 4312 USA Tel 1 800 525 2000 www eatonelectrical com...

Reviews: