background image

 

 

Specification are subject to change without notice. Copyright 2009 Eaton Industries Pty Ltd 

Technical Specification –PVD40-500-V-C 

Tvss Doc# 510092 

Page 2 of 2 

 

 

INSTALLATION 

  

PROCEDURE:

 

1. CHECK 

 

Always work safely – disconnect power before 
making connections. 

 

All wiring must be carried out by suitably qualified 
personnel according to the applicable standards. 

 

Check for correct operating voltage and power 
system. This model (PVD40-500-V-C) is designed 
for DC power systems in the range of 450 – 
500VDC. 

If your power system is a different 

voltage, this model is not suitable

. Please 

contact your supplier. 

 

Always use the correct size HRC fuses.  

 

Always use Gg or Gl-rated fuses. Do not use 
delay types or ‘semiconductor’ fuses. 

2. INSTALL 

 

Locate a fuse position as close as possible to the 
incoming DC breaker. 

 

Install fuse holders or fuse-switch if required. 

 

Locate a suitable position for the SPD, ensuring 
adequate space for cables. Do not install above 
heat-generating objects or in any position that is 
exposed to weather. 

3. CONNECT 

 

Connect wiring - refer to connection diagrams. If 
using stranded cable, always use wire ferrules for 
lowest resistance and to prevent damage to the 
wire. 

 

 Keep termination length as short as possible. 

Do 

not wire in extra loops or cable length. 

 

Use a suitably-rated cable for alarm connections. 
Cable should be rated for operation at the system 
voltage and should be 0.5mm

2

 to 1.5mm

2

 

4. NOTES: 

 

125A fuses are rated such for maximum surge 
rating. On services below 125A, fit a fuse lower in 
value to the service size.

 

 

Wiring from fuse to SPD is carrying surge currents 
only, not load current. This means that smaller 
cables may be used than is normal for the current 
rating. 

 

 

If using under-sized cables, some energy 
authorities require double insulation (i.e. sleeving) 
of the cables.

 

 

Unplug the alarm connector for termination.

 

 

Do not Megger test cabling with unit connected – 
unit may be damaged.

 

 

EARTHING 

For proper operation, all surge diverters rely upon a good 
earth connection: 

  The main earth wire (from earth link on switchboard to 

ground rod or system) MUST be as short and direct as 
possible.  Extra cable must not be looped. 

  Earth connections from the unit to earth link 

MUST

 be 

as short as possible. 

 

 

Failure to consider the above points can result in 
improper operation of the unit and possible damage to 
the installation. 

 
Electrical configuration diagram 
 

 

 
 
 
 
 
 
 

Reviews: