background image

 

 

Specification are subject to change without notice. Copyright 2009 Eaton Industries Pty Ltd 

Technical Specification –PVD40-500-V-C 

Tvss Doc# 510092 

Page 1 of 2 

 

PVD40-500-V-C Surge Diverter 

 
Class II SPD arrester in accordance with IEC 
61643-1:2005. Compliance to UL1449 ed.3. 
 
500vdc Surge Protection for PV installations 

FEATURES 

 

2 mode protve - Earth, -ve - Earth 

 

Compact solution for solar inverter protection 

 

2 pole wide Din 43880 form factor 

 

Replaceable plug in protection module 

 

Includes floating-contact alarm output

 

 

Available in a range of DC voltages to 1000vdc.

 

 

Applications 

 

Grid inter active inverters 

 

Standby inverters 

 

 

FUNCTIONAL DESCRIPTION  

The PVD40-500-V-C is designed to protect 
photovoltaic solar panel inverters from harmful 
transients by diverting excess energy to earth from 
+ve and –ve conductors to earth.   

This model (PVD40-500-V-C) is designed for 450-
500vdc systems. If your power system is a 
different voltage, this model is NOT suitable

.  

 
Please contact your supplier for a suitable model to 
suit your application. 

 
OPERATION 

The operational status of the unit is shown by a flag 
indicator on the front of the unit. In normal operation, 
the flag is green. If the unit becomes damaged, the 
flag changes to red, indicating that replacement is 
necessary. A contact alarm output is fitted to the 
base of unit and will change over if the unit is faulty.

 

 

WARRANTY

  

Eaton warrants this unit against faulty parts and 
workmanship for a period of 12 months from the date 
of purchase. If this product fails to operate correctly, 
please contact your Eaton representative. This 
warranty doesn’t cover neglect or intentional misuse. 
As this product is intended for use in electrically 
harsh environments no claim is made of suitability for 
purpose. This unit is designed to reduce the 
likelihood of damage. Please also note that an 
excessive surge, such as from a direct lightning strike 
to the site or a power system fault, may cause 
damage to the unit and render it inoperable. A unit 
that has been damaged in this way is not 
warrantable. 

 

 

 
 

For installation details,  

See over page. 

SPECIFICATIONS

 

Manufacturers name and model 

Eaton PVD40-500-V-C 

Method of mounting 

Din rail mount 

Input voltage 

450 - 500VDC 

Maximum continuous operating 
voltage - MCOV 

530VDC 

Service type 

+VE – E , -VE - E 

Test classification  

Class II 

Supply current 

<10mA 

Initial clamp voltage  

 500VDC 

Maximum rated surge current - 
Ismax 8/20us   

 
40kA   

Nominal surge current –  
Inom 8/20us  

 
20kA 

Residual voltage (Vpl) @ Inom 
20kA, 8/20uS  at terminals 

1.6kV 

Nominal surge lifetime (In)  

20kA (8/20uS), 20 times 

Internal protection 

MOV thermal disconnect 
device. 

External disconnector  
 ( if required ) 

Gg/Gl HRC fuses,  125A 
maximum.

 

Terminations 

Main terminals multi strand 
25mm

2   

Alarm terminals 1.5mm

2

Alarms/indicators 

Flag indicator,  alarm relay  
contact 250VAC/24VDC, 2A 

Location Category 

Indoor 

Enclosure rating 

IP20 

Applicable standards. 

IEC61643-1:2005, UL1449 
ed.3  

Dimensions 

90mm (H) x 36mm (W) x 
68mm (D). excluding alarm 
connector 

Weight 

180g 

Environment 

-10 to 60C, 0-90%RH 

Warranty 

12 months, workmanship 
and materials 

Reviews: