Specification are subject to change without notice. Copyright 2009 Eaton Industries Pty Ltd
Technical Specification –PVD40-500-V-C
Tvss Doc# 510092
Page 1 of 2
PVD40-500-V-C Surge Diverter
Class II SPD arrester in accordance with IEC
61643-1:2005. Compliance to UL1449 ed.3.
500vdc Surge Protection for PV installations
FEATURES
•
2 mode protve - Earth, -ve - Earth
•
Compact solution for solar inverter protection
•
2 pole wide Din 43880 form factor
•
Replaceable plug in protection module
•
Includes floating-contact alarm output
•
Available in a range of DC voltages to 1000vdc.
Applications
•
Grid inter active inverters
•
Standby inverters
FUNCTIONAL DESCRIPTION
The PVD40-500-V-C is designed to protect
photovoltaic solar panel inverters from harmful
transients by diverting excess energy to earth from
+ve and –ve conductors to earth.
.
This model (PVD40-500-V-C) is designed for 450-
500vdc systems. If your power system is a
different voltage, this model is NOT suitable
.
Please contact your supplier for a suitable model to
suit your application.
OPERATION
The operational status of the unit is shown by a flag
indicator on the front of the unit. In normal operation,
the flag is green. If the unit becomes damaged, the
flag changes to red, indicating that replacement is
necessary. A contact alarm output is fitted to the
base of unit and will change over if the unit is faulty.
WARRANTY
Eaton warrants this unit against faulty parts and
workmanship for a period of 12 months from the date
of purchase. If this product fails to operate correctly,
please contact your Eaton representative. This
warranty doesn’t cover neglect or intentional misuse.
As this product is intended for use in electrically
harsh environments no claim is made of suitability for
purpose. This unit is designed to reduce the
likelihood of damage. Please also note that an
excessive surge, such as from a direct lightning strike
to the site or a power system fault, may cause
damage to the unit and render it inoperable. A unit
that has been damaged in this way is not
warrantable.
For installation details,
See over page.
SPECIFICATIONS
Manufacturers name and model
Eaton PVD40-500-V-C
Method of mounting
Din rail mount
Input voltage
450 - 500VDC
Maximum continuous operating
voltage - MCOV
530VDC
Service type
+VE – E , -VE - E
Test classification
Class II
Supply current
<10mA
Initial clamp voltage
500VDC
Maximum rated surge current -
Ismax 8/20us
40kA
Nominal surge current –
Inom 8/20us
20kA
Residual voltage (Vpl) @ Inom
20kA, 8/20uS at terminals
1.6kV
Nominal surge lifetime (In)
20kA (8/20uS), 20 times
Internal protection
MOV thermal disconnect
device.
External disconnector
( if required )
Gg/Gl HRC fuses, 125A
maximum.
Terminations
Main terminals multi strand
25mm
2
Alarm terminals 1.5mm
2
Alarms/indicators
Flag indicator, alarm relay
contact 250VAC/24VDC, 2A
Location Category
Indoor
Enclosure rating
IP20
Applicable standards.
IEC61643-1:2005, UL1449
ed.3
Dimensions
90mm (H) x 36mm (W) x
68mm (D). excluding alarm
connector
Weight
180g
Environment
-10 to 60C, 0-90%RH
Warranty
12 months, workmanship
and materials