![Eaton PowerXpert 9395P-600/200 Installation And Operation Manual Download Page 35](http://html1.mh-extra.com/html/eaton/powerxpert-9395p-600-200/powerxpert-9395p-600-200_installation-and-operation-manual_527289035.webp)
UPS INSTALLATION PLAN AND UNPACKING
Eaton
Power Xpert 9395P-600 (380V-600V) UPS Installation and Operation Manual
S
P-164000710 Rev 1
www.eaton.com/powerquality
3-3
Table 3‐1. UPS Cabinet Maximum Weights
Model
Section
Maximum Weight
kg (lb)
Shipping
Installed
Eaton 9395P-600/600
Eaton 9395P-600/550
Eaton 9395P-600/500
Eaton 9395P-600/450
Eaton 9395P-600/400
ISBM (CSS)
+ 2 UPMs
TBA
TBA
FI-UPM
TBA
TBA
Eaton 9395P-600/300
Eaton 9395P-600/275
Eaton 9395P-600/250
Eaton 9395P-600/225
Eaton 9395P-600/200
ISBM (CSS)
+ 1 UPM
TBA
TBA
NOTE
CSS = Continuous Static Switch
NOTE
Table 3-3 describes power ratings of each model.
The UPS cabinet uses forced air cooling to regulate internal component temperature.
Air inlets are in the front of the cabinet and outlets are in the top. Allow clearance in
front of and above each cabinet for proper air circulation. The clearances required
around the UPS cabinet are shown in Table 3‐2. Dimensions are in millimeters
(inches).
Table 3‐2. UPS Cabinet Clearances
From Top of Cabinet
457.2 mm (18
”
) minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36
”
) working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the UPS are:
S
40°C (32–104°F) at elevations up to 1000m without derating
S
For 300 kW and 600 kW: 0 to 35°C at elevations up to 1000m without derating.
S
Recommended Operating Range: 20–25°C (68–77°F)
S
Maximum Relative Humidity:
95%, non-condensing
NOTE
If Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental
requirements supersede the UPS requirements. Operating temperatures above the recommended range will
result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to
Eaton's Terms and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price
Book for more information. These documents can be found at www.eaton.com/powerquality or contact an
Eaton service representative for information on how to obtain copies.