![Eaton PowerXL DE1 series Quick Start Manual Download Page 13](http://html1.mh-extra.com/html/eaton/powerxl-de1-series/powerxl-de1-series_quick-start-manual_4032311013.webp)
PowerXL DE1 VSS Quick Start Guide
PowerXL DE1 Series Variable Speed Starter
MN040015EN– February 2015
www.eaton.com
12
Step 4 – LED Light Indicators and Faults
The
Run
,
Status
, and
Fault Code
LEDs will behave as follows:
Run
LED – Operation Signal (GREEN):
Flashes every 2 seconds when the main voltage is applied, there is no enable input signal
present at DI1 or DI2, and there are no active fault messages
Solid/continuous when the device is running and there is an input enable (start) signal on DI1
or DI2
No illumination when the main power is removed or there is an internal device fault
Status
LED – Status Message (RED):
Flashes with the Fault Code LED when there is an undervoltage condition
Solid/continuous illumination with
Fault Code
LED in the event of an internal communication
fault (DE1 malfunctioning)
Fault Code
LED – Fault Signal (RED/YELLOW):
Cyclical Red flashing/pulse sequence with 2 second pauses observe Table 4
Flashes Red with the
Status
LED when there is an undervoltage condition
Solid/continuous Red illumination with
Status
LED in the event of an internal communication
fault (DE1 malfunctioning)
Solid/continuous Yellow when DE1 VSS DC braking is active
Figure 12. LED Status Light Layout