4 CANopen communication settings
4.7 Parameters
CANopen for DA1, DC1, DE11
09/16 MN040019EN
www.eaton.com
41
4.7.1 Parameters on DA1 devices
Table 21: Parameters on DA1 devices
CANOpen
Index
[hex]
Para
meter
Designation
Access
Scaling
Value range
Data
format
rw/
ro
RUN/
STOP
2065
P1-01
f-max
rw
RUN
3000
≙
50.0Hz
P1-02 - 5 x P1-09
(max.: 500.0 Hz / 30000 rpm)
U16
2066
P1-02
f-min
rw
RUN
3000
≙
50.0Hz
0.0 Hz - P1-01
U16
2067
P1-03
t-acc
rw
RUN
300
≙
30.0s
0.00 s - 6000 s
U16
2068
P1-04
t-dec
rw
RUN
300
≙
30.0s
0.00 s - 6000 s
U16
2069
P1-05
Stop Mode
rw
RUN
0 - 4
U16
206 A
P1-06
Energy Optimizer
rw
RUN
0 - 1
WORD
206B
P1-07
Motor Nom Voltage
rw
STOP
230
≙
230 V
0 - U
e
U16
206C
P1-08
Motor Nom Current
rw
STOP
1
≙
0.1A
0.1 I
e
- I
e
U16
206D
P1-09
Motor Nom Frequency
rw
STOP
50
≙
50Hz
10 Hz - 500 Hz
U16
206E
P1-10
Motor Nom Speed
rw
RUN
1500
≙
1500rpm
0 / 200 rpm - 30000 rpm
U16
206F
P1-11
V-Boost
rw
STOP
-1
≙
Auto
0
≙
disabled
1
≙
0.1%
0 - Auto / 0 - 30.0 % P1-07
S16
2070
P1-12
Local ProcessData Source
rw
STOP
0 - 13
U16
2071
P1-13
DI Config Select
rw
STOP
0 - 21
U16
2072
P1-14
Password
rw
RUN
0 - 30000
U16
20C9
P2-01
f-Fix1
rw
RUN
3000
≙
50.0 Hz
P1-02 (min: 0 Hz / 0 rpm) - P1-01
(max: 500.0 Hz / 30000 rpm)
U16
20CA
P2-02
f-Fix2
rw
RUN
3000
≙
50.0 Hz
P1-02 (min: 0 Hz / 0 rpm) - P1-01
(max: 500.0 Hz / 30000 rpm)
U16
20CB
P2-03
f-Fix3
rw
RUN
3000
≙
50.0 Hz
P1-02 (min: 0 Hz / 0 rpm) - P1-01
(max: 500.0 Hz / 30000 rpm)
U16
20CC
P2-04
f-Fix4
rw
RUN
3000
≙
50.0 Hz
P1-02 (min: 0 Hz / 0 rpm) - P1-01
(max: 500.0 Hz / 30000 rpm)
U16
20CD
P2-05
f-Fix5
rw
RUN
3000
≙
50.0 Hz
P1-02 (min: 0 Hz / 0 rpm) - P1-01
(max: 500.0 Hz / 30000 rpm)
U16
20CE
P2-06
f-Fix6
rw
RUN
3000
≙
50.0 Hz
P1-02 (min: 0 Hz / 0 rpm) - P1-01
(max: 500.0 Hz / 30000 rpm)
U16
20CF
P2-07
f-Fix7
rw
RUN
3000
≙
50.0 Hz
P1-02 (min: 0 Hz / 0 rpm) - P1-01
(max: 500.0 Hz / 30000 rpm)
U16
20D0
P2-08
f-Fix8
rw
RUN
3000
≙
50.0 Hz
P1-02 (min: 0 Hz / 0 rpm) - P1-01
(max: 500.0 Hz / 30000 rpm)
U16
20D1
P2-09
f-Skip1
rw
RUN
3000
≙
50.0 Hz
P1-02 (min: 0 Hz / 0 rpm) - P1-01
(max: 500.0 Hz / 30000 rpm)
U16
20D2
P2-10
f-SkipBand1
rw
RUN
3000
≙
50.0Hz
P1-02 (min: 0 Hz / 0 rpm) - P1-01
(max: 500.0 Hz / 30000 rpm)
U16
20D3
P2-11
ADO1 Function & Mode
rw
RUN
0 - 11
U16
20D4
P2-12
AO1 SignalFormat
rw
RUN
0 - 5
U16
Summary of Contents for PowerXL DA1