Eaton Powerware SPD120i/A Installation Instructions Download Page 2

 

 

Specification are subject to change without notice. Copyright 2005 Eaton Power Quality Pty Ltd 

Technical Specification –SPD120i/A 

Tvss Doc# 510077 

Page 2 of 2 

 

Web: 

http://www.powerware.com.au

 Phone: 1300 UPS UPS

 

INSTALLATION 

Refer to the procedure and diagram shown to connect the 
SPD120i/A. 

PROCEDURE:

 

1. CHECK 

• 

Always work safely – disconnect power before making 
connections. 

• 

All wiring must be carried out by suitably qualified 
personnel according to the applicable standards. 

• 

Check for correct operating voltage and power system. 
This model (SPD120i/A) is designed for power systems 
in the range of 220-277V(380-480V). 

If your power 

system is “delta” (i.e. ungrounded), or of a different 
voltage, this model is not suitable

. Please contact 

your supplier. 

• 

** For installation adjacent to an M.E.N. link, use the L-N 
mode. Insert insulated link as shown. 

• 

** For installations remote from the M.E.N., use the L-E 
mode. Remove link. A separate N-E protector is required 
Contact your distributor for information. 

• 

Always use the correct size HRC fuses.  

• 

For services >125A, use 125A fuses. For services 
<125A, use one step below service fuses (i.e. 80A 
service =63A fuses). DO NOT USE AN MCB. 

• 

Always use Gg or Gl-rated fuses. Do not use delay types 
or ‘semiconductor’ fuses. 

• 

Consider fitting a fuse-switch or a separate isolation 
switch to facilitate safe maintenance in the future. 

2. INSTALL 

• 

Locate a fuse position as close as possible to the Main 
Switch. 

• 

Install fuseholders or fuse-switch. 

• 

Locate a suitable position for the SPD, ensuring 
adequate space for cables. Do not install above heat-
generating objects or in any position that is exposed to 
weather. 

• 

Install unit to DIN-rail in switchboard or cabinet. 

3. CONNECT 

• 

Connect wiring - refer to connection diagrams. If using 
stranded cable, always use wire ferrules for lowest 
resistance and to prevent damage to the wire. 

• 

Use a suitably-rated cable for power connections. Cable 
should be rated for operation at the system voltage and 
should be 4mm

2

 to 16mm

2

• 

Use short cables for phase, neutral and earth 
connections or protection will be reduced.

 

• 

Use a suitably-rated cable for alarm connections. Cable 
should be rated for operation at the system voltage and 
should be 0.5mm

2

 to 1.5mm

2

 

4. NOTES: 

• 

125A fuses are rated such for maximum surge rating. 
On services below125A, use the correspondingly lower 
sized fuse (i.e.80A service = 63A fuse).

 

• 

Wiring from fuse to SPD is carrying surge currents only, 
not load current. This means that smaller cables may be 
used than is normal for the current rating. 

 

• 

If using under-sized cables, some energy authorities 
require double insulation (i.e. sleeving) of the cables.

 

• 

Maximum alarm relay resistive load is 5A.

 

• 

It is recommended not to connect the alarm contacts to 
AC mains circuits if possible, to prevent flashover from 
surges on the AC line. Connect to a PLC or BMS if 
available.

 

• 

Do not Megger test cabling with unit connected – unit 
may be damaged.

 

 

EARTHING 

For proper operation, all surge diverters rely upon a good earth 
connection: 

• 

The main earth wire (from earth link on switchboard to ground 
rod or system) MUST be at least 6mm diameter (preferably 
larger) and should be as short as possible.  

• 

Earth connections from the unit to neutral or earth link MUST 
be as short as possible. 

 

Failure to consider the above points can result in improper 
operation of the unit and possible damage to the installation. 

 

 

L-E mode 
connections:

 

L-N mode 
connections:

 

Reviews: