MBM INSTALLATION
Eaton 9395 Maintenance Bypass Module Installation and Operation Manual
S
164201719 Rev 3
www.eaton.com/powerquality
4-19
4.3.4
Standalone Cabinet Installation
To install an MBM located separately from the Eaton 9395 UPS cabinet (see
Figure 4‐16 and Figure 4‐17):
1.
Verify that the UPS is properly installed and secured. Refer to the applicable
Eaton 9395 Installation and Operation manual listed in paragraph 1.7 on page 1-4
for installation instructions.
2.
Using a forklift, move the MBM cabinet to the final installed location.
3.
Carefully lower the MBM cabinet until the cabinet base contacts the floor.
4.
Unfasten the MBM front door latch and swing the doors open (see Figure 4‐1 on
page 4-2).
5.
Remove the door by removing the retaining screws located inside the door at the
top and bottom hinge pivot points, then lift the door off. Save the retaining
screws for reinstallation of the door.
6.
Remove the screws securing the top and bottom internal safety shield panels,
and remove the panels to gain access to the inside of the cabinet.
7.
If permanently mounting the system, proceed to Step 8; otherwise, continue to
Step 10.
8.
Using the retained hardware, reinstall the shipping brackets removed in
paragraph 4.2, Steps 2 and 3 to the left and right sides of the MBM cabinet with
the angle facing outward (see Figure 4‐1 and Figure 4‐2).
9.
Secure the cabinet to the floor with customer-supplied hardware.
10.