Chapter 2
Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the
equipment and save this manual for future reference.
D A N G E R
This UPS contains
LETHAL VOLTAGES
. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY
. There are
NO USER SERVICEABLE PARTS
inside the UPS.
W A R N I N G
S
This UPS contains its own energy source (batteries). The output receptacles may carry
live voltage even when the UPS is not connected to an AC supply.
S
For 230V models, the output receptacles may remain electrically live. If the input power
source in your application is wired line-to-neutral (as in most European applications), the
voltage to the output receptacles is 0V. With line-to-line input wiring, the voltage to the
output receptacles is 115V (measured from line-to-ground or line-to-neutral, depending
on the UPS wiring).
S
Do not remove or unplug the input cord when the UPS is turned on. This removes the
safety ground from the UPS and the equipment connected to the UPS.
S
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature
must not exceed 40
°
C (104
°
F). Do not operate near water or excessive humidity (95%
maximum).
S
To comply with international standards and wiring regulations, the total equipment
connected to the output of this UPS must not have an earth leakage current greater than
3.5 milliamperes.