INSTALLATION REFERENCE
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
A−35
16.
Terminals are UL and CSA rated at 90°C. See Table K through Table M for
input power cable terminations. Section A.5 shows the location of the input
power cable terminals inside the PDU cabinet.
17.
DO NOT overtighten the terminal lugs to prevent stripping the threads. Tighten
lugs to the torque values in Table K through Table M.
Table K. Powerware 225 kVA PDU Input Power Cable Terminations (208V)
Terminal Function
Rating
(kVA)
Main Breaker
Rating
Terminal
Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type and Size
Screw
AC Input to Main
Breaker CB1
30
125A
A
Phase A
1 – #2
8 (75)
Slotted
B
Phase B
1 – #2
8 (75)
Slotted
C
Phase C
1 – #2
8 (75)
Slotted
N
Neutral
2 – 1/0
31 (275)
5/16
"
Hex
50
175A
A
Phase A
1 – 2/0
8 (75)
Slotted
B
Phase B
1 – 2/0
8 (75)
Slotted
C
Phase C
1 – 2/0
8 (75)
Slotted
N
Neutral
2 – 1/0
31 (275)
5/16
"
Hex
75
300A
A
Phase A
2 – 1/0
31 (275)
5/16
"
Hex
B
Phase B
2 – 1/0
31 (275)
5/16
"
Hex
C
Phase C
2 – 1/0
31 (275)
5/16
"
Hex
N
Neutral
2 – 3/0
31 (275)
5/16
"
Hex
100
350A
A
Phase A
2 – 2/0
31 (275)
5/16
"
Hex
B
Phase B
2 – 2/0
31 (275)
5/16
"
Hex
C
Phase C
2 – 2/0
31 (275)
5/16
"
Hex
N
Neutral
3 – 2/0
31 (275)
5/16
"
Hex
125
450A
A
Phase A
2 – 3/0
31 (275)
5/16
"
Hex
B
Phase B
2 – 3/0
31 (275)
5/16
"
Hex
C
Phase C
2 – 3/0
31 (275)
5/16
"
Hex
N
Neutral
3 – 3/0
31 (275)
5/16
"
Hex
150
600A
A
Phase A
2 – 300 kcmil
31 (275)
5/16
"
Hex
B
Phase B
2 – 300 kcmil
31 (275)
5/16
"
Hex
C
Phase C
2 – 300 kcmil
31 (275)
5/16
"
Hex
N
Neutral
4 – 3/0
31 (275)
5/16
"
Hex
Customer Ground
All
All
G
Ground
1 – 1/0
31 (275)
5/16
"
Hex