PDU OPERATING INSTRUCTIONS
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
6−9
Table 6-1. Status Indicators
Indicator
Status
Description
Green
On
The PDU output is energized.
Flashing
An informational event has occurred. Press any control panel pushbutton once to acknowledge the event.
The indicator then returns to steady illumination..
The LCD displays this event as a Notice.
Yellow
On
One or more phases are overloaded, or a transformer is overloaded.
Yellow
Off
The PDU main input breaker is open.
Red
Flashing or On
The PDU has an active alarm and requires immediate attention. All alarms are accompanied by an audible
horn. The Alarm indicator may be illuminated along with other indicators. To acknowledge the alarm and
silence the horn, press any control panel pushbutton once. The alarm indicator then returns to steady
illumination.
The LCD shows the highest priority active alarms.
6.2.2
System Events
When the PDU is operating, it continually monitors itself and the incoming utility
power. System events on the PDU can be indicated by horns, lights, messages, or all
three.
Select
EVENTS
from the menu bar on the main menu screen to look at the active
events screen. This screen shows any currently active alarms, notices, or commands.
For more information on using the events screen, see paragraph 6.2.7, on page 6−12.
S
System Event Horns
– The system event horn beeps to alert an operator that an
event needing attention is taking place. The horn cycles at a half−second rate.
S
System Event Indicators
– The status indicators on the PDU control panel work with
the event horn to let the operator know when the PDU is operating in any mode
other than normal. Only the ON indicator is visible during normal PDU operation.
The other indicators illuminate to indicate alarms or events. When an alarm occurs,
first check these indicators to see what type of event has taken place. For
descriptions of the status indicators, see paragraph 6.2.1.
S
System Event Messages
– When a system event occurs, a message appears on the
LCD in the PDU status area. This message is also written to the Active Events Log
and may be added to the History Log. The messages are divided into four
categories: alarms, notices, status, and commands.