Effective June 2009

Remote latch check switch (LCS) for

Magnum low voltage circuit breakers

 

Soep 2e: 

Remove the accessory (if installed) from the indicated 

position on the accessory tray by lifting its lock up and sliding the 

accessory toward the front of the breaker. Then lift accessory up 

and out of tray. Do not disconnect the wiring.

Figure 3. Soep 2

Soep 3e:

 Connect three wires from the LCS to secondary block 

positions B28, B29, and B30 per wire markings. Check that all  

wire terminals are secure by pulling gently. Then push the LCS into 

center slot in the accessory tray. Make sure the LCS is fully seated.

Figure 4. Soep 3

Soep 4e: 

Reinstall any accessory that was removed in Step 2.

Soep 5e: 

Test the installation.

 cautiOn

dO nOt tOuch the interiOr Of the breaker while the spring is 

charged. push the Off buttOn first tO ensure that the breaker 

is nOt clOsed. failure tO fOllOw this actiOn cOuld result in a 

seriOus injury. 

Measure the continuity of the LCS with an Ohm meter during this 

step. With the breaker OPEN and DISCHARGED, push and release 

the OFF button. The LCS should not operate. This is indicated by 

the absence of an audible “click” from the switch. The Ohm meter 

verifies there is no change in continuity of the LCS contacts.

Remove This Accessory 

for Easier Access

Lock

LCS

Secondary Block

Now charge the breaker using the manual charge handle. When the 

breaker is fully charged, repeat the above test by pushing the OFF 

button again. An audible “click” from the LCS should be heard and 

continuity as measured by the Ohm meter should change.

Figure 5. Soep 5

Soep 6e: 

Reinstall the front cover. Push the CLOSE and then the 

OPEN pushbuttons to discharge all energy from the mechanism, 

leaving it in an OPENED and DISCHARGED status.

Disclaimer of warranties and  

limitation of liability

The information, recommendations, descriptions, and safety  

notations in this document are based on Eaton Corporation’s 

(“Eaton”) experience and judgment, and may not cover all  

contingencies. If further information is required, an Eaton sales 

office should be consulted.
Sale of the product shown in this literature is subject to the terms 

and conditions outlined in appropriate Eaton selling policies or other  

contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, 

WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING 

WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR 

MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET  

OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY 

SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. 

THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME  

PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. 
In no event will Eaton be responsible to the purchaser or user in 

contract, in tort (including negligence), strict liability, or otherwise 

for any special, indirect, incidental, or consequential damage or loss 

whatsoever, including but not limited to damage or loss of use of 

equipment, plant or power system, cost of capital, loss of power, 

additional expenses in the use of existing power facilities, or claims 

against the purchaser or user by its customers resulting from the 

use of the information, recommendations, and descriptions  

contained herein.
The information contained in this manual is subject to change  

without notice.

Trip Latch 

Lever

Reviews: