 warning

(1) Only qualified electrical persOnnel shOuld 

be permitted tO wOrk On the equipment.  

(2) always de-energize primary and  

secOndary circuits if a circuit breaker  

cannOt be remOved tO a safe wOrk lOcatiOn. 

(3) drawOut circuit breakers shOuld be 

levered (racked) Out tO the discOnnect  

pOsitiOn. 

(4) all circuit breakers shOuld be switched  

tO the Off pOsitiOn and mechanism springs 

discharged. 

failure tO fOllOw these steps fOr all  

prOcedures described in this instructiOn  

leaflet cOuld result in death, bOdily injury,  

Or prOperty damage.

Section 1: General information

A latch check switch (LCS) indicates when the 

circuit breaker is “ready to close” (

Figure 1

). 

The external version used for remote indication 

consists of 1 Form C contact wired to the circuit 

breaker secondary contacts for integration into 

external control schemes. 

Noee:

N

Wiring the LCS for remote indication directly in 

series with the SR accessory is not recommended as 

this will override the “anti-pump” feature. 

Required oNNls

• 

1/4-inch drive ratchet

• 

10 mm socket

Kio paros idenoificaoiNn

Refer to 

Figure 1

 for visual identification of the 

contents of kit.

Figure 1. CNnoenos Nf Kio

Section 2: Installation of  

external remote LCS

To install the LCS, proceed with the following  

six steps:

Soep 1e: 

Remove the front cover by unscrewing 

the hex-head captive bolts (four for three-pole, 

six for four-pole) that join the cover to the breaker 

housing using a 10 mm 1/4-inch drive socket. 

Then hold the charge handle down at about a  

45-degree angle to pull off the cover. 

Figure 2. Soep 1

LCS (external 

version shown)

Mounting Bolts