Figure 70. Front mounting of top lifting bracket.
Figure 71. Rear mounting of top lifting bracket.
3.5.2 Lifting
When an XGIS vertical section is ready for installation, an overhead
lifter or portable floor lifter can be used to move the vertical section
in conjunction with the Eaton top lifting bracket.
When a vertical section is to be lifted, position the lifter over the
vertical section and insert hooks into the vertical section top lifting
bracket’s holes. Once the lifting hooks are securely seated in the
lifting bracket holes, the vertical section can be carefully lifted and
moved. Lifting chains should each be of equal length, at least 1
meter long each.
3.6 Storage
If the XGIS vertical section is to be placed in storage, maximum
protection can be obtained by keeping it packed as shipped. Before
placing it in storage, checks should be made to make sure that the
vertical sections are free from shipping damage and is in satisfactory
operating condition.
The storage area where XGIS vertical sections are stored must be
clean, dry and well-ventilated, with an interior temperature of no less
than 23o F. (-5o C.) Check the area periodically for condensation.
Store the vertical section packages upright, and do not stack them.
Indoor storage should be in a building with sufficient heat and air
circulation to prevent condensation. If the building is not heated, the
same general rule for heat as for outdoor storage, as noted below,
should be applied.
Outdoor storage of the switchgear element is NOT recommended.
If unavoidable, the outdoor location must be well drained and
sheltered from sun, rain, snow, corrosive fumes, dirt, falling objects
and excessive moisture. Containers should be arranged to permit
free circulation of air on all sides and temporary heaters should be
used to minimize condensation. Moisture can cause rusting of metal
parts and deterioration of medium-voltage insulation. A heat level
of approximately 400 watts for each 100 cubic feet of volume is
recommended with the heaters distributed uniformly throughout the
structure near the floor.
3.7 Tools and accessories
Manual operating T-handle for 3PDS Catalog Number (included with
XGIS Switchgear)
87A1027H01
Note:
main bus sections come in kits that include cleaning cloths
with solvent, and silicone grease. If more is needed,
SSIS accessories:
•
cleaning cloths soaked in cleaning solvent (must be used; no
alternative is acceptable)
87A1045H01
•
Main bus silicone grease
87A1046H01
•
Tee connector silicone grease:
Top-mount voltage transformer installation/removal tool (refer to
and
) Catalog Number
87A1060G01.
The following tools and accessories are recommended for
installation and commissioning (not provided with the XGIS
switchgear):
•
SF
6
leak detector - Eaton recommends Protec Equipment
Resources
DILO 3-033-R200
•
Gas Handling Equipment - Eaton recommends Relation
Corporation
LM090
•
Portable voltage transformer lifting system (refer to section
Voltage transformer installation and removal) Catalog Number
87A1090G01.
3.8 XGIS gas insulated switchgear vertical section weights
The weights in
below are for vertical sections including
three-position disconnect switches and circuit breakers (as
appropriate), incoming bus bar, bus fused VTs and cable CTs but
excluding control and protection relays, and other custom features.
Table 8. Approximate vertical section weights (see exclusions
above)
Vertical
section
A rating
Feeder /
incoming Lb.
(kg.)
Bus tie
Lb. (kg.)
Bus
sectionalizer
Lb. (kg.)
Disconnector
Lb. (kg.)
1250
3262 (1483)
3223 (1465)
3003 (1365)
3222 (1465)
2000
3669 (1668)
3633 (1651)
3411 (1550)
3629 (1650)
2500
3769 (1713)
3733 (1697)
3511 (1596)
3729 (1695)
1 gal. bucket
87A1098H01
5 gal. bucket
87A1098H02
40 lb. bucket
87A1098H03