background image

Explanation of the panel control

Explanation of the circuit-breaker control

From service position to earthed position

Power Xpert™ UX operation

(Summary of user manual 6063308_G01 03)

Position indicator for 

circuit-breaker truck

(TEST or SERVICE)

1

Position indicator for 

earthing switch (ON or OFF)

10

Emergency operating facility 

to switch the circuit-breaker 

to ON position (mechanical)

11

Emergency operating facility 

to switch the circuit-breaker 

to OFF position (mechanical)

12

Drive shaft to fi t the hand 

crank for rack IN-OUT 

circuit-breaker

13

Operating shaft for manual 

operation of the integral 

earthing switch with cover 

and padlock facility

14

Position indicator for 

circuit-breaker (ON or OFF)

8

Push button for switching 

the circuit-breaker to the 

OFF position (electrical)

9

Voltage detection system

3

Release to access the

drive shaft for rack IN-OUT 

circuit-breaker

5

Circuit-breaker 

(compartment) door

6

Push button for switching 

the circuit-breaker to the 

ON position (electrical)

2

Viewing window

4

Cable (compartment) door

7

Switch OFF the circuit-breaker

a.  Open the circuit-breaker via the OFF

push-button (9).

b.  Check that the circuit-breaker is OFF.

Withdrawal from SERVICE to TEST

 position

a.

Fit the hand crank on the drive shaft (1

3

).

b.

 Turn the hand crank anti-clockwise until

the unit reach the TEST position.

c.

 Remove the hand crank.

d.

 With the unit in the TEST position the

 

circuit-breaker door (6) can be opened,

 

if

needed.

Switch ON the earthing switch

a.  Make sure that cables are 

‘dead’

        .

If provided, check the indicator of 
the voltage detection system (3).

d.  Turn the handle clockwise to move

the earthing switch to the ON position.

e.  Remove the operating handle.
f.  The earthing switch can be padlocked

in the ON position, if required.

g.  With the earthing switch in the ON

position cables are earthed and the
cable door (7) can be opened.

b.

 Open the cover to access the operating

 

shaft (

14).

c.

 Press down the interlock driver and

 

insert the operating handle.

Red arrows and dots are

not visible:

 cable is dead.

When red arrows and dots are

visible:

 cable is live!

Secondary connector

A

Manual charging handle

B

Operation counter

D

Spring charged/discharged 

indicator

C

Manual close button

E

OPEN/CLOSED indicator

F

Manual open button

G

Reviews: