Installation
4-30
Eaton
®
Power Xpert
®
9395C UPS Installation and Operation Manual P-164000821—Rev 01
www.eaton.com/powerquality
4.7.3
X-Slot Connections
For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-10).
To install wiring to connections:
1.
If not already installed, install the LAN drops.
2.
Unfasten the front door latch and swing the door open (see Figure 4-1).
3.
Remove the right interface entry conduit landing plate to drill or punch holes (see Figure 4-14).
4.
Reinstall the interface entry plate and install the conduit.
5.
Route and install the LAN and other cables to the appropriate X-Slot cards. See Figure 4-18 and
Figure 4-23 for X-Slot communication bay locations.
6.
Close the door and secure the latch.
7.
Refer to the manual supplied with the X-Slot card for operator instructions.
Figure 4-23. X-Slot Communication Bays
NOTE
LAN drops for use with X-Slot cards must be provided by the customer.
NOTE
When installing external wiring to X-Slot cards, conduit must be installed to the UPS
cabinet. When installing internal wiring to X-Slot terminals, route the wiring through
the internal opening in the X-Slot communication bay.
X-Slot Communication Bay 4
TB3
TB1 and TB2
X-Slot Communication Bay 2
X-Slot Communication Bay 1
X-Slot Communication Bay 3