44
9. Modbus register map
Power XPert® release triP unit for MagnuM PXr circuit breakers
MN013015EN January 2022 www.eaton.com
Table 25. Modbus protection group data (continued).
func.
code
register
number
address
(hex)
setpoint name
r/w
Definition
3013
0x0BC4
SD pickup (Isd)
See
note
PXR 20 (read only)
15 = 1.5xIr
20 = 2.0xIr
25 = 2.5xIr
40 = 4.0xIr
50 = 5.0xIr
60 = 6.0xIr
70 = 7.0xIr
80 = 8.0xIr
100 = 10.0xIr
PXR 25 (read/write) valid range:
15 to 100
3014
0x0BC5
SD time (tsd)
See
note
PXR 20 (read only)
5 = 50ms
10 = 100ms
20 = 200ms
30 = 300ms
40 = 400ms
50 = 500ms
PXR 25 (read/write) valid range:
5 to 50
3015
0x0BC6
Inst. pickup (Ii)
See
note
PXR 20 (read only)
0 = OFF
20 = 2xI
n
40 = 4xI
n
50 = 5xI
n
60 = 6xI
n
70 =7xI
n
80 = 8xI
n
100 = 10xI
n
120 = 12xI
n
150 = 15xI
n
PXR 25 (read/write) valid range:
0, 20 to 150
3,4,6
3016
0x0BC7
Ground sensing
R/W
0 = residual
1 = source/zero sequence
3017
0x0BC8
Ground action
R/W
0 = trip
1 = alarm
2 = OFF
3018
0x0BC9
Ground slope
R/W
0 = flat
1 = I
2
T
3019
0x0BCA
Ground pickup (I
g
)
See
note
PXR 20 (read only)
0 = OFF
20 = 0.2xI
n
40 = 0.4xI
n
60 = 0.6xI
n
80 = 0.8xI
n
100 = 1.0xI
n
PXR 25 (read/write) valid range:
0, 20 to 100
3020
0x0BCB
Ground time(t
g
)
See
note
PXR 20 (read only)
10 = 0.1s
20 = 0.2s
30 = 0.3s
40 = 0.4s
50 = 0.5s
PXR 25 (read/write) valid range:
10 to 50
3,4,6
3021
0x0BCC
GF thermal memory
R/W
0 = disable
1 = enable
3,4,6
3022
0x0BCD
Neutral protection ratio
R/W
0 = 0%
60 = 60%
100 = 100%
3,4,6
3023
0x0BCE
High load alarm 2
R/W
Value is percentage x I
r
.
Valid range: 50 to 115, must be > high load 1.
3,4,6
3024
0x0BCF
GF pre-alarm
R/W
Value is percentage x I
r
.
Valid range: 50 to 100.
3,4,6
3025
0x0BD0
Thermal memory alarm
R/W
Value is percentage x I
r
.
Valid range: 50 to 100.
3,4,6
Ground fault sensing
R/W
0 = residual
1 = source ground/zero sequence