INSTALLATION
Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual
S
164201687 Rev 4
www.eaton.com/powerquality
4-15
4.3.4
Internal Battery String Connection
All battery cabinets arrive at the site with each battery connection string electrically
disconnected. To interconnect the battery tray strings:
1.
Verify that all battery breakers are in the OFF position.
2.
FOR 1085 ONLY:
Connect the string of battery trays by mating the loose red
connector from each tray to the fixed black connector mounted on the front edge
of the tray above. Connect the top and bottom tray connectors to the mating
cabinet connectors to complete the battery string connections (see Figure 4‐13).
3.
FOR 1085HR ONLY:
Connect the string of battery trays by mating the loose
black connector with the blue locking mechanism from each tray to the fixed
black connector mounted on the front edge of the tray below. Connect the top
and bottom tray connectors to the mating cabinet connectors to complete the
battery string connections (see Figure 4‐14).
4.
Repeat Step 2 or Step 3 for each battery cabinet, and then proceed to Step 5.
5.
Replace the doors that were removed in paragraph 4.2.
6.
Secure all battery cabinets by closing and latching the doors.
7.
Return to the appropriate Power Xpert 9395 UPS Installation and Operation
manual, as referenced in paragraph 1.7, to complete the UPS wiring.
Battery Breaker
Fixed Right Battery
Power Connector
(black)
String Connectors
(red)
Figure 4‐13. 1085 Battery String Connection