INSTALLATION
Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual
S
164201687 Rev 4
www.eaton.com/powerquality
4-3
W
A
R
N
I
N
G
RISK OF INSTABILITY. Turning the jacking bolts unevenly may cause the cabinet to become unbalanced. To
prevent tipping the cabinet, raise and lower the jacking bolts evenly.
C
A
U
T
I
O
N
CABINET MAY TIP. The battery cabinet should only be raised approximately 3 mm (1/8”) above the floor (just
enough to allow removal of the 4
6 supports).
7.
Remove the hardware loosened in Step 5. Pull the 4
6 supports out from under
the battery cabinet. Discard or recycle them in a responsible manner.
C
A
U
T
I
O
N
CABINET MAY FALL. Do not loosen the hardware attaching the side or front supports to the cabinet base, or
the front and side supports to each other, at this time. The cabinet must be lowered by the jacking bolts
before the supports can be removed.
8.
Carefully and evenly
lower the cabinet by turning each jacking bolt consecutively two
full turns (maximum)
until the casters contact the floor, and the cabinet is no longer
supported by the jacking bolts.
9.
Remove the jacking bolts and discard or recycle them in a responsible manner.
10.
Remove the hardware holding the front, rear, and side supports to the cabinet
base. Discard or recycle the hardware and support brackets in a responsible
manner.
11.
Roll the battery cabinet to its final location.
12.
Repeat Steps 3 through 11 for each cabinet you are preparing to install.
4.3
Model 1085 or 1085HR Battery Cabinet Installation
The 9395 Model 1085 or 1085HR battery cabinet is designed to be installed in a
standalone
configuration. Customer-supplied conduit and wiring is installed externally
between each battery cabinet and the UPS or UPS disconnect. Battery cabinets may
be installed adjacent to the UPS or in a separate location.
C
A
U
T
I
O
N
The 1085
and
1085HR
battery cabinets CANNOT be intermixed. Serious damage to equipment may result.
4.3.1
Mechanical Installation
Use this procedure to install the battery cabinet. The battery cabinet shown in
Figure 4‐2 is located adjacent to the UPS cabinet, but may be located in a separate
location.
There are no battery cabinet‐to‐UPS mechanical attachment requirements for this
type of system. However, individual battery cabinets must be attached and grounded
to each other, as described in this section.