4
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
11..11
U
UP
PS
S S
Sttaannddaarrdd FFeeaattuurreess
The UPS has many standard features that provide cost–effective and consistently reliable power protection.
The descriptions in this section provide a brief overview of the UPS standard features.
11..11..11
IInnssttaallllaattiioonn FFeeaattuurreess
Cabinets can be permanently bolted to the floor.
Power and control wiring can be routed through the top or bottom of the cabinet with connections made to
easily accessible terminals. External sensing and monitoring control wire must be installed in accordance with
Class 1 wiring methods.
11..11..22
C
Coonnttrrooll P
Paanneell
The control panel, located on the front of the UPS, contains a liquid crystal display (LCD) and pushbutton
switches to control the operation of the UPS and to display the status of the UPS system. See
operating instructions for additional information.
11..11..33
C
Cuussttoom
meerr IInntteerrffaaccee
•
Building Alarm Monitoring
– Up to five inputs in the UPS are available to connect the facility's alarm
system contacts. Some system configurations may limit the number of inputs available. The UPS uses
these inputs to monitor the building alarms in addition to the UPS status. See
for additional information.
•
Alarm Contact
– One alarm contact is provided for connection to equipment at the facility, such as a light,
an audible alarm, or a computer terminal. The equipment connected to this contact alerts you to a UPS
alarm. See
for additional information.
•
X-Slot Communication Bays
– Four communication bays are standard equipment. One to four optional X-
Slot
®
connectivity cards can be installed in the UPS module at any time. X-Slot cards are quickly installed at
the front of the UPS and are hot-pluggable. See
for additional information.
11..11..44
A
Addvvaanncceedd B
Baatttteerryy M
Maannaaggeem
meenntt
A three-stage charging system increases battery service life by optimizing recharge time, and protects batteries
from damage due to high current charging and inverter ripple currents. Charging at high currents can overheat
and damage batteries.
11..11..55
P
Poow
weerr M
Maannaaggeem
meenntt S
Sooffttw
waarree
Eaton LanSafe
®
Power Management Software is bundled as part of the Software Suite CD shipped with the
UPS. See
for additional information.
11..22
O
Oppttiioonnss aanndd A
Acccceessssoorriieess
Contact an Eaton sales representative for information about the following options.
11..22..11
IInntteeggrraatteedd B
Baatttteerryy C
Caabbiinneettss
Battery backup protection can be provided by equipping the UPS system with up to four Eaton 9395 battery
cabinets containing sealed lead–acid, maintenance–free batteries. The battery cabinets are available with a 240-
cell configuration. The cabinets are designed for
standalone
installation and may be installed adjacent to the
UPS or in a separate location. The recommended installation location for adjacent battery cabinets is on the
right side of the UPS cabinet to allow for future expansion using an external module.
Consult the
Power Expert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual
for
specifics on battery cabinet usage with the PowerXpert 9395.
Summary of Contents for Power Xpert 9395
Page 8: ......
Page 269: ...16420172515 164201725 15 ...