Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
1100..22..22 U
UP
PS
S O
Ouuttppuutt
UPS Output Capacity
100% rated current
Output Voltage Regulation
±1% (10% to 100% load
Output Voltage Adjustment (Nominal
+/
3%)
400 Vac nominal, adjustable from 388 Vac to 412 Vac
480 Vac nominal, adjustable from 466 Vac to 494 Vac
Output Voltage Harmonic Content
1.5% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
See
,
,
or
Output Voltage Balance
3% for 100% maximum load imbalance (linear load)
Output Voltage Phase Displacement
3° for 100% maximum load imbalance (linear load)
Output Transients
±5% (10% to 100% load)
Frequency Regulation
±0.1 Hz free running
Synchronous to Bypass
+10% to -10% ±3%
Frequency Slew Rate
1 Hz per second maximum
Load Compatibility
0.9 pF Leading
0.8 pF Lagging
Overload Capability
110% for 10 minutes
125% for 30 seconds
150% for 10 seconds
NOTE
The 110% overload capability in the above table is based on the kVA label rating of the
UPS. The 125% and 150% overloads are based on the non-derated hardware capability
of the UPS.
1100..22..33 U
UP
PS
S EEnnvviirroonnm
meennttaall
Operating Temperature
0 to 40 °C (32 to 104
F) without derating. The recommended operating
temperature is 25
C (77
F).
Operating Altitude
Maximum 1000m (3000 ft) at 40 °C without derating
Storage Temperature
–25 to +60 °C, excluding batteries (prolonged storage above 40 °C causes rapid
battery self discharge).
Relative Humidity (Operating and Storage)
5% to 95% maximum non-condensing
Acoustical Noise
76 dB at a 1m distance, A weighted
EMI Suppression
Meets FCC Regulation 47, Part 15, for class A devices
Electrostatic Discharge (ESD) Immunity
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without damage
and with no disturbance or adverse effect to the critical load.