Figure 154. FI-UPM Air Filter Location
FI-UPM Air Filter
99..22..33
P
PEER
RIIO
OD
DIIC
C M
Maaiinntteennaannccee
Periodic inspections of the UPS should be made to determine if components, wiring, and connections exhibit
evidence of overheating. Particular attention should be given to bolted connections. Maintenance procedures
should specify that the bolted connections be retorqued to values listed in this manual.
99..22..44
A
AN
NN
NU
UA
ALL M
Maaiinntteennaannccee
Annual preventive maintenance should be performed only by authorized service personnel familiar with
maintenance and servicing of the UPS system. Contact an Eaton service representative for more information
about service offerings.
99..22..55
B
BA
ATTTTEER
RYY M
Maaiinntteennaannccee
Contact an Eaton service representative for battery maintenance. Battery replacement and maintenance should
be performed only by authorized service personnel
99..33
IInnssttaalllliinngg B
Baatttteerriieess
NOTE
There is no manual DC disconnect device within the UPS.