Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
7
•
X-Slot Cards
– Optional X-Slot cards support several protocols, such as SNMP, HTTP, IBM
®
AS/400
®
, and
Modbus
®
RTU.
•
eNotify Remote Monitoring and Diagnostics Service
– An optional service that provides 24/7 remote
monitoring of 43 alarms, temperature/humidity and battery charge information, daily heartbeat check, and
monthly report. The service also provides customer notification of significant alarms, remote diagnostics,
and dispatch of technicians. A PXGX Card is required in an X-Slot communication bay. An optional
Environmental Monitoring Probe is required for temperature/humidity monitoring.
See
for additional information on monitoring and communication features.
11..33
B
Baatttteerryy S
Syysstteem
m
Although not provided with the UPS, a battery system is required to provide emergency short-term backup
power to safeguard operation during brownouts, blackouts, and other power interruptions. The battery system
should be equipped with lead–acid batteries. An external battery disconnect switch must be used.
The UPMs may be powered with either a common or separate battery system. In a common battery system,
single and multiple UPMs are powered from one common battery source. In a separate battery system,
multiple UPMs are each powered from separate battery sources.
UPMs in distributed bypass and parallel systems must use a separate battery system.
Consult the
Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual
for
specifics on battery cabinet usage with the PowerXpert 9395.
A supplemental 48 Vdc shunt trip signal for the battery disconnect device is provided by the UPS, but is not
required for normal operation.
NOTE
The 9395 system can trip a maximum of six battery cabinets total. This applies to both
the 1085 standard and High Rate series batteries. If more than six battery cabinets in
total are needed in a separate UPM battery configuration, DO NOT hook up the shunt
trips.
11..44
U
Ussiinngg TThhiiss M
Maannuuaall
This manual describes how to install and operate the Power Xpert 9395 9395 550/275 UPS cabinet. Read and
understand the procedures described in this manual to ensure trouble-free installation and operation. In
particular, be thoroughly familiar with the REPO procedure (see
Using the Remote Emergency Power-off Switch
).
The information in this manual is divided into sections and chapters. The system, options, and accessories
being installed dictate which parts of this manual should be read. At a minimum, Chapters 1 through 4 and
Chapter 7 should be examined.
Read through each procedure before beginning the procedure. Perform only those procedures that apply to the
UPS system being installed or operated.
11..55
C
Coonnvveennttiioonnss U
Usseedd iinn TThhiiss M
Maannuuaall
This manual uses these type conventions:
•
Bold type
highlights important concepts in discussions, key terms in procedures, and menu options, or
represents a command or option that you type or enter at a prompt.
•
Italic type
highlights notes and new terms where they are defined.
•
Screen type
represents information that appears on the screen or LCD.