Instruction Leaflet 

IL0131080EN

Effective January 2019

3-way multi-family drawout cable interlock kit - type 32 - NF 

  

  

EATON

 www.eaton.com

WARNING

(1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO 

WORK ON THE EQUIPMENT. 

 

(2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A 

CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK LOCATION. 

 

(3) DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED (RACKED) OUT TO 

THE DISCONNECT POSITION. 

 

(4) ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF POSITION 

AND MECHANISM SPRINGS DISCHARGED. 

 

FAILURE TO FOLLOW THESE WARNINGS FOR ALL PROCEDURES 

DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH, 

BODILY INJURY, OR PROPERTY DAMAGE.

WARNING

THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS 

HAVE TO BE FOLLOWED. OBSERVE THE FIVE SAFETY RULES: 

– DISCONNECTING 

–  ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY RESTARTED 

–   VERIFY ISOLATION FROM THE SUPPLY 

–   EARTHING AND SHORT-CIRCUITING 

–   COVERING OR PROVIDING BARRIERS TO ADJACENT LIVE PARTS 

 

DISCONNECT THE EQUIPMENT FROM THE SUPPLY. USE ONLY AUTHORIZED 

SPARE PARTS IN THE REPAIR OF THE EQUIPMENT. THE SPECIFIED 

MAINTENANCE INTERVALS AS WELL AS THE INSTRUCTIONS FOR REPAIR 

AND EXCHANGE MUST BE STRICTLY ADHERED TO PREVENT INJURY TO 

PERSONNEL AND DAMAGE TO THE SWITCHBOARD.

WARNING

MECHANICAL INTERLOCKS FOR SYSTEMS WITH ONE OR TWO SUPPLIES 

SWITCHED ON AT ALL TIMES. IN THE EVENT THAT BOTH SUPPLY 

SWITCHING DEVICES ARE IN THE OPEN POSITION, THERE IS A POSSIBILITY 

THAT A CLOSE SIGNAL TO ALL THREE SWITCHING DEVICES COULD CAUSE 

MOMENTARY PARALLELING. IF THIS IS UNDESIRABLE, THE USER MAY 

WANT TO INCLUDE A SEPARATE MECHANICAL AND/OR ELECTRICAL 

INTERLOCK TO PREVENT SIMULTANEOUS CLOSING COMMANDS BEING 

SENT TO BOTH OF THE NORMAL SUPPLY SWITCHING DEVICES (A AND C) 

AND THE TIE SWITCHING DEVICE (B) UNDER ALL CONDITIONS.

General information

This information leaflet provides detailed installation instructions for 

installing and interconnecting one drawout Type NF frame breaker 

to another type of low voltage circuit breaker (LVCB) in any position 

(see A, B, C in 

Table 1

) for a Type 32 interlock configuration as 

shown in 

Figure 1

 . When purchasing kits for a Type 32 interlock 

configuration setup, additional interlock kits (the types of interlock 

kits and the other breakers on which they can be installed that are 

compatible with this kit are listed in 

Table 2

) are required for the 

other two breakers as well as the interconnecting cable kits (three 

are required) . 
For Type 32 interlock configurations, the mechanical interlock holds 

one of the breakers tripped or open (prevents closure) when the 

other two are closed . A lever assembly is mounted on each breaker 

and interfaces with the poles haft and trip bar . The lever assemblies 

are interconnected with cables provided in interconnecting cable 

kits (listed in 

Table 3

) that are compatible with this interlock kit . The 

cable kits, purchased separately, each contain two cables and can be 

used for any orientation of the breakers according to the installation 

recommendations in 

Step 5

 .

Refer to 

Figure 2

 and 

Figure 3

 for identification of interlock kit and 

interconnecting cable kit contents, respectively .

Breaker A

Breaker B

Breaker C

Type 32 cable routing

Type 32 cable routing

Figure 1. Cable routing for Type 32 interlock configurations

Table 1.  Type 32 interlock logic

Type 32 (six cable)

Breaker
A

B

C

A

B

C

Allowed states or conditions

0

0

0

1

0

0

0

1

0

0

0

1

1

1

0

0

1

1

1

0

1

0 = open

1 = closed

Summary of Contents for Power Defense 32-NF

Page 1: ...NRX IZMX Power Defense Contents Description Page General information 2 Installation of three way cable interlock 4 Functional test of interlock assembly 9 3 way multi family drawout cable interlock ki...

Page 2: ...AL AND OR ELECTRICAL INTERLOCK TO PREVENT SIMULTANEOUS CLOSING COMMANDS BEING SENT TO BOTH OF THE NORMAL SUPPLY SWITCHING DEVICES A AND C AND THE TIE SWITCHING DEVICE B UNDER ALL CONDITIONS General in...

Page 3: ...IZMX MIL CAB2440 2 3 0 m 10 ft IZMX MIL CAB3050 2 a Cable kits are purchased separately as needed A B C D E F H G I M3 x 8 mm flathead screw 2x Lock washer 3x M6 x 12 mm hex bolt 3x Interlock assembl...

Page 4: ...The drive arm should be oriented as shown in Figure 4 and Figure 5 Torque to 0 3 0 6 N m 3 5 in lb Step 2 Install the trip pin F to the trip bar using an M3 x 8 mm flathead screw C while holding the...

Page 5: ...s refer to Figure 10 For example a cable connected to the Drive Lever Pull Swivel Fitting on Breaker A must connect to the Driven Lever Pull Swivel Fitting on Breaker B ATTENTION FIGURE 9 SHOWS THE TY...

Page 6: ...gure 10 follow the directions below see Figure 11 1 Remove upper nut from end of rod of cable assembly 2 Slide rubber boot toward tip of rod 3 Unthread outer bulkhead nut and slide nut and lock washer...

Page 7: ...rive lever Compression spring Swivel fitting Lower nuts Stop at end of thread Raise cable assembly until threaded portion of bulkhead fitting enters slotted hole in cable bracket threads show above br...

Page 8: ...0 2 mm Figure 13 Driven And lever position with interconnected push breaker open and pull breaker closed Lever plate Gap 0 4 mm Connected breaker open Gap Connected breaker closed Figure 14 Driven An...

Page 9: ...end long rod Bulkhead Rubber boot Outer bulkhead nut Lock washers 2 Pull swivel Upper nut 22 2 mm 0 875 inch cable tube spacer Lower nuts Driven And lever Pull swivel Upper nut 30 5 mm 1 2 inch cable...

Page 10: ...time OPEN Breaker C CHARGE and CLOSE Breakers A and B Breaker C should be interlocked held OPEN not able to CLOSE CHARGE and attempt to CLOSE Breaker C it should not respond to CLOSE attempt no noise...

Page 11: ...agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN...

Reviews: