Using the device
Settings
Before commissioning the motor-protective circuit-breaker,
the rated motor current must be set with the setting dial on
the PKE (
The setting dial on the trip block has 16 discrete positions for
the following settings:
Table 8:
Overview of settings on the trip block
Test
The motor-protective circuit-breaker features a test function
(
When the test function is operated with the motor-protective
circuit-breaker switched on, the PKE trips and all main
contacts open. The lines downstream of the PKE can then be
tested for zero voltage. To allow the powered-on motor-
protective circuit-breaker PKE to trip in its test position, a
current corresponding at least with the minimum set value of
the trip block must flow.
0.3 - 1.2 A
0.30
0.33
0.36
0.40
0.43
0.47
0.50
0.56
0.63
0.70
0.77
0.83
0.90
1.00
1.10
1.20
1 - 4 A
1.00
1.10
1.20
1.30
1.42
1.55
1.70
1.90
2.10
2.40
2.60
2.80
3.00
3.30
3.70
4.00
3 - 12 A
3.00
3.30
3.60
4.00
4.30
4.70
5.00
5.60
6.30
7.00
7.70
8.30
9.00
10.00
11.00
12.00
8 - 32 A
8.00
8.80
9.70
10.50
11.50
12.50
13.50
15.00
17.00
19.00
20.50
22.00
24.00
27.00
29.00
32.00
h
To ensure its safety function, motor-protective circuit-
breaker PKE must be tested with the built-in test function
at least once a year.
j
Danger!
Faulty devices must not be opened and repaired. They
must be replaced by specialist personnel.