Eaton PDI WaveStar Color Monitor Setup and Operation Manual P-164001109—Rev 01
17
Figure 13. Modbus RTU Setup
On
SETUP
screen, touch
DEVICES/MODBUS
The
DEVICES/MODBUS
screen defines the Modbus
network and device chain as well as set the banner
name for the header.
Modbus Device Chain:
Banner
Name displayed on top line.
Number of Devices
should equal
number of devices connected in
Monitor’s downstream device chain.
Upstream Modbus:
Address of Monitor on upstream side
Baud rate (9600/19200/38400)
Parity (even/odd/none)
Downstream Modbus
Network
characteristics are fixed and cannot
currently be modified.
44..22..22
M
Mooddbbuuss R
RTTU
U S
Seettuupp
Downstream Modbus
settings cannot be changed.
Upstream Modbus
provides network characteristics on the upstream side of the Monitor.
•
Address is the address that the upstream Modbus client, such as the Building Management System
(BMS), uses to address the Monitor. The downstream device addresses are incremented sequentially
from this address. So if the Monitor has address 20, the next three devices will appear 21, 22, and 23 to
the upstream client device. (See
, “Modbus Addressing”.)
•
Upstream Modbus
settings for
Baud
rate and
Parity
must match those for the upstream Modbus client.
44..22..33
TTC
CP
P//IIP
P aanndd M
Mooddbbuuss TTC
CP
P//IIP
P S
Seettuupp
For TCP/IP, the customer must provide an Ethernet cable connected to the Ethernet port (RJ45 header J11) on
the Monitor. (See
, "Color Monitor Network Connections".)
On the
SETUP
screen, touch
NETWORK/SNMP
to display the network parameters for TCP/IP (11, 14).
The following must be specified for Modbus TCP/IP:
•
IP Address
•
Subnet Mask
•
Gateway
Each connected monitor must be assigned a unique address. DHCP is not supported.
Summary of Contents for PDI WaveStar
Page 1: ...p n P 164001109 Revision 01 Setup and Operation Manual Eaton PDI WaveStar Color Monitor...
Page 4: ......
Page 12: ...2 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Safety...
Page 60: ...50 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Web Pages...
Page 62: ...52 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Glossary...
Page 64: ...54 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Bibliography...
Page 68: ...P 16400110901 P 164001109 01...