Use ferrules with flexible and highly flexible conductors.
Bei feindrähtigen und hochflexiblen Leitern Aderendhülsen verwenden.
Pour les conducteurs souples et extra-souples, utiliser des embouts.
Para conductores flexibles y muy flexibles deben utilizarse terminales.
Per conduttori flessibili e altamente flessibili utilizzare capicorda.
对于多股和非常容易弯曲的线缆可以使用线缆衬套
Д
.
Use of Terminal Cover NZM3-XKSA on UL/CSA models:
– Mechanical (tunnel) lug connector kits …XKA… come supplied with terminal cover NZM3-XKSA.
Top and bottom portions of the terminal cover are mounted as shown in above diagrams and installation is always required.
– Terminal cover NZM3-XKSA maintains electrical clearances and provides protection against accidental contact
with live parts in the incoming and outgoing supply circuit terminations of the Circuit-Breaker or switch
–
NZM3-XKA2
Maximum allowed rated current: 400 A
5b
1
2
31 Nm
(274.37 lb-in)
35 mm
(1.38 ”)
60 mm
(2.36 ”)
8 mm
1 x 50 - 240 mm
2
2 x 50 - 240 mm
2
1 x AWG 0 - 500 kcmil
2 x AWG 0 - 500 kcmil
6
Z 2
1 Nm
(8.85 lb-in)
XKSA
XKSA
1
2