Use ferrules with flexible and highly flexible conductors.
Bei feindrähtigen und hochflexiblen Leitern Aderendhülsen verwenden.
Pour les conducteurs souples et extra-souples, utiliser des embouts.
Para conductores flexibles y muy flexibles deben utilizarse terminales.
Per conduttori flessibili e altamente flessibili utilizzare capicorda.

对于多股和非常容易弯曲的线缆可以使用线缆衬套

Д

 

   

 

 

 

 

 

.

Use of Terminal Cover NZM3-XKSA on UL/CSA models:

– Mechanical (tunnel) lug connector kits …XKA… come supplied with terminal cover NZM3-XKSA.

Top and bottom portions of the terminal cover are mounted as shown in above diagrams and installation is always required.

– Terminal cover NZM3-XKSA maintains electrical clearances and provides protection against accidental contact

with live parts in the incoming and outgoing supply circuit terminations of the Circuit-Breaker or switch

NZM3-XKA2

 Maximum allowed rated current: 400 A

5b

1

2

31 Nm

 (274.37 lb-in)

35 mm

(1.38 ”)

60 mm

(2.36 ”)

8 mm

1 x 50 - 240 mm

2

2 x 50 - 240 mm

2

1 x AWG 0 - 500 kcmil
2 x AWG 0 - 500 kcmil

6

Z 2

1 Nm

(8.85 lb-in)

XKSA

XKSA

1

2