![Eaton Network Shutdown Module V3 User Manual Download Page 48](http://html1.mh-extra.com/html/eaton/network-shutdown-module-v3/network-shutdown-module-v3_user-manual_3811996048.webp)
www.eaton.com
Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE
Page 47/65
z
Customized actions
These user-customized actions give access to additional functions.
Action name
Role
User notification
A message is displayed on the screen of the protected machine, its importance is
indicated by a colored symbol:
- Green: Information message.
- Yellow: Alarm message.
- Red: Critical alarm message.
- Grey: Communication Lost.
Message broadcast
to the administrator
A message is sent over the network to administrators connected to the server
protected by Network Shutdown Module.
Note
: This action only occurs if the "Administrator notification" box is checked on the
Configuration Network Shutdown Module
screen.
Message broadcast
to users
A message is sent over the network to users connected to the server protected by
Network Shutdown Module.
Note
: This action only occurs if the "Administrator notification" box is checked on the
Configuration Network Shutdown Module
screen.
System shutdown
System and UPS shutdown according to the
configured parameters
.
Execute a program
Execution of an application (.exe file) or script (.bat, .cmd, .sh … file).
Send an E-mail
Send an alarm message by e-mail using the SMTP network server.
7.8.1.2 Add an action
Follow these steps to add a new action:
1. Click on the
Add
button
2. Enter the name of the new action (unique action identifier)
3. Select the type of action to be added
Execute
Send an e-mail
7.8.1.3 «System Shutdown» Action
When personalizing the action
System shutdown
in the action configuration page, you can choose the type
of shutdown:
z
For Windows, there is a choice of shutdown depending on your system and your requirements.
Click on the
Parameter
button, to read the help on the shutdown type:
z
For Linux, only the shutdown option is currently supported.