Protection
Contextual help of the web interface – 57
•
•
•
3.5.2 Agent shutdown sequencing
3.5.2.1 Agent shutdown sequence timing
All agents that are connected to the Network Module are displayed in tables by power sources.
Primary
Group 1
Group 2
The 'local agent' setting is used for setting for example a minimum shutdown duration, or a power down delay for a load segment
that has no registered shutdown agents.
One use case would be a load segment that powers network equipment that needs to stay on while servers and storage perform
their orderly shutdown.
The tables include the following details: