Eaton MTL661 Instruction Manual Download Page 7

DRAFT - 20 November 2014

DRAFT - 20 November 2014

3

INM 660 rev 14

Press 

 for 3 seconds 

To return to the operator level, PROG must be pressed for three 

seconds. If no keys are pressed for 2 minutes, the 
MTL661/2/3/5 will leave the SETUP mode automatically.

3 .1 .2   Setup functions and variables

1

DISPLAY

11

UNIT

no unit - MM – CM – M – MEtER 
– MIL – IN – Ft – Yd – FAtH – SQFt 
– ML – L – NL – AL – M3 – NM3 – 
AM3 – GAL – USGAL – IGAL – bbL 
– CUFt – MG – G – KG – tON – OZ 
– Lb – ST – QR – CWT – PSI – PDIG 
– MbAR – MbARG – bAR – bARG 
– PA – MPA – PAG – KPA – KPAG – 
MMH2O – MH2O – INH2O – MMHG 
– INHG – °C – °F – K – P – RPM – % 
– PPM – MA – A

12

TIME

/SEC - /S - /MIN - /M  - /HR - /H - /DAY 
- /D - no unit

13

DECIMALS

0 - 1 - 2 - 3 - 4 (Ref: displayed value)

14

OFFSET

–99,999 -  +99,999

15

SPAN

0.0001 - +99,999 unit/time-unit 

16

DIRECTION

reverse -  normal

17

CURRENT

enable / disable

18

PERCENTAGE

enable / disable

19

PIEGRAPH 

enable / disable

2

SENSOR

21

FORMULA

interpolation, square root

22

FILTER

00 -  99

23

CALIBRATE LOW 

default -  calibrate -  set

24

CALIBRATE HIGH 

default -  calibrate -  set

3

OTHERS

31

MODEL

32

SOFTWARE VERSION

33

SERIAL NO.

34

PASSWORD

0000 -  9999

35

TAGNUMBER

0000000 -  9999999

3 .1 .3   Details of SETUP functions

1 - DISPLAY

11 UNIT

This determines the measurement unit that will be displayed. A 
choice can be made from the range of units shown in Section 3.2.2.

Alteration of the measurement unit will have consequences for 
other SETUP-level values. 

Please note that the Span has to be adapted as well; the calculation 
is not done automatically.

12 TIME 

For flowrate calculations, a time unit can be set. The flowrate can 
be calculated per second (/SEC or /S); minute (/MIN or /M); hour (/
HR or /H) or day (/DAY or /D).

Select “———” if no time unit is desired.

13 DECIMALS 

This setting determines the number of digits following the decimal 
point. The following can be selected:

 

000000   -  11111.1  -  2222.22   -  333.333

14 OFFSET 

The offset is the minimum 

displayed

 value of the range of 

measurement. This needs to be programmed into the display.

Example: Setting a temperature range

For a temperature range of 20°C to 120°C, the offset at the minimum 
signal of 4mA is 20°C.

 

Therefore make offset 

20°C

The minus for a negative value can be selected by pressing 

the 

 and 

 button simultaneously.

15 SPAN 

The span is the difference between the maximum and minimum 

displayed

 values for the range of 4 to 20mA inputs. 

Example: Setting a temperature range

For a temperature range of 20°C to 120°C, the span is the difference 
between the top and the bottom values of the range, i.e. 100°C.

 

Therefore set span to 

100°C

Example:  Programming the span for a flowrate

Assume that a sensor generates 20mA at a flowrate of 2,481.3 litres/
minute; then select the unit as “Litres”, the time unit as “minute” 
and the number of decimals as “1”.

Set the span as 2481.3
Enter for SETUP - 15: “2481.3”.

16 DIRECTION

If the display is required to increase in value as the input current 
increases, select the scale direction “normal”. Alternatively, select 
“reverse” if the display is required to decrease as the input current 
rises.

17 CURRENT

Select “enable” if you want the actual current value to be displayed 
for the operator.

18 PERCENTAGE

Select “enable” if you want to the 0% value and 100% value to be 
displayed for the operator.

19 PIEGRAPH 

The piegraph (displayed at operator level) displays the input signal 
as a percentage. The minimum signal (setup 23) corresponds to 0% 
and the maximum signal (setup 24) to 100%.

With this function, the piegraph can be enabled / disabled.

NOTE

Figure 7

Summary of Contents for MTL661

Page 1: ...DRAFT 20 November 2014 MTL661 2 3 5 IS Loop Powered Indicators September 2016 INM 660 rev 14 Instruction manual MTL intrinsic safety solutions...

Page 2: ...v 14 DECLARATION OF CONFORMITY A printed version of the Declaration of Conformity has been provided separately within the original shipment of goods However you can find a copy of the latest version a...

Page 3: ...ming SETUP level 2 4 INSTALLATION 5 4 1 General directions 5 4 2 Installation surrounding conditions 5 4 3 Enclosure Dimensions 5 4 4 Hardware and connections 5 4 5 Accessories for mounting displays 6...

Page 4: ...l other electrical apparatus installed in hazardous areas this apparatus must only be installed operated and maintained by competent personnel Such personnel shall have undergone training which includ...

Page 5: ...d MTL665 B A model number with a B suffix indicates that it has a backlight For Zone 2 mounting the MTL661 B NA and MTL662 B NA versions must be used The manual is divided into two main sections The d...

Page 6: ...s been pressed To return to OPERATOR level Display current If activated the actual input current will be displayed after pressing SELECT Display 0 100 If activated the 0 value 4mA and 100 value 20mA w...

Page 7: ...ECIMALS This setting determines the number of digits following the decimal point The following can be selected 000000 11111 1 2222 22 333 333 14 OFFSET The offset is the minimum displayed value of the...

Page 8: ...ngs can be selected CALIBRATE With this setting the input will be calibrated with the actual 4mA value After pressing ENTER CAL SET will be displayed as soon as the indicator completes its calibration...

Page 9: ...r holes see Section 8 are provided through the side flanges to assist with the mounting of the indicator See also Section 4 5 for details of wall and pipe mounting the MTL661 B 4 4 2 Mounting the MTL6...

Page 10: ...de Description Used with WMP66 Wall mounting plate MTL661 MTL663 PMA66 Pipe mounting adaptor MTL661 MTL663 PIP66 Pipe mounting kit MTL661 MTL663 GAS660 Spare gaskets pk of 10 MTL661 MTL663 GAS665 Spar...

Page 11: ...r the final display Remove the three bracket screws and attach the WMP66 plate so that the studs for mounting the display are positioned horizontally i e left and the right Fit the display onto the st...

Page 12: ...ormally mounted in the hazardous area c This apparatus has been designed and manufactured so as to provide protection against all the relevant additional hazards referred to in Annex II of the directi...

Page 13: ...G Example of top label for models MTL661 B MTL662 B and MTL663 B Example of rear label for models MTL661 B MTL662 B and MTL663 B Example of rear label for model MTL665 B Example of inside label for mo...

Page 14: ...ld Yes GRP 500g A Case style A front view side view panel cutout 120 4 72 130 5 12 14 0 55 31 1 22 115 4 53 98 2 36 Case style B 144 5 67 front view 72 2 83 30 1 18 16 0 63 138 5 43 68 2 68 side view...

Page 15: ...DRAFT 20 November 2014 11 INM 660 rev 14 9 CSA CONTROL DRAWING...

Page 16: ...Russia LLC Elektrozavodskaya Str 33 Building 4 Moscow 107076 Russia Tel 7 495 981 3770 Fax 7 495 981 3771 E mail mtlrussia eaton com SINGAPORE Cooper Crouse Hinds Pte Ltd No 2 Serangoon North Avenue 5...

Reviews: