5 Function blocks
5.9 CI, High-speed incremental value counter
250
Manual
11/10 MN05002001Z-EN www.eaton.com
5.9.2 Wiring of the function block
You wire the function block in the circuit diagram with its coils and its
contacts.
5.9.2.1 Coils
The coils of the function block is used in the circuit diagram.
5.9.2.2 Contacts
The contacts of the function block are evaluated in the circuit diagram. A
closed contact indicates:
5.9.2.3 Example of a high-speed incremental counter:
Figure 152: Wiring the function block coils
The count inputs of function block CI01 are already permanently assigned to
device inputs I1 and I2. The coils of the function block are connected directly
here to the device inputs.
→
Note that the digital inputs I1 to I4 are permanently assigned to
the incremental counter function blocks provided:
•
I1: Counter input for counter CI01, channel A.
•
I2: Counter input for counter CI01, channel B.
•
I3: Counter input for counter CI02, channel A.
•
I4: Counter input for counter CI02, channel B.
Parameters
Function
⑤
CI..EN
Selective activation of the function block
⑥
CI..RE
Reset the actual value to zero
⑦
CI..SE
Transfer of the start value on a rising edge.
Parameters
Function
①
CI..OF
Reaching or exceeding the upper limit setpoint
②
CI..FB
Reaching or falling below the lower limit setpoint
③
CI..ZE
Actual value equals zero
④
CI..CY
Value range exceeded, If it is closed, the function block retains the value of the last valid
operation.
I 05---------------------------
Ä
CI01EN
I 06---------------------------
Ä
CI01RE
I 07---------------------------
Ä
CI01SE
Summary of Contents for MFD-Titan
Page 1: ...Operating Instructions Multi Function Display MFD Titan 11 10 MN05002001Z EN ...
Page 4: ...II ...
Page 22: ...0 About This Manual 0 5 Writing conventions 18 Manual 11 10 MN05002001Z EN www eaton com ...
Page 42: ...1 MFD 1 6 MFD operation 38 Manual 11 10 MN05002001Z EN www eaton com ...
Page 472: ...8 MFD Settings 8 5 Setting time 468 Manual 11 10 MN05002001Z EN www eaton com ...
Page 490: ...9 Inside MFD 9 8 Device Version Number 486 Manual 11 10 MN05002001Z EN www eaton com ...