Installation instructions 

1.  Normal  precautions  should  be  taken  to  guard  against  swarf/dust  entering  isolators  and  any  remaining 

debris in the bottom of the box should be removed. 

 

2.  All  unused  sub  circuit  positions  must  have  an  associated  blank  plate  fitted  in  the  box  cover.  Ensure  all 

terminal shields are replaced. 

 

3.  Appropriate Isolator devices: EMS631N, EMS1001N 

 

4.  The EAN Full Metal Box and appropriate devices have been type tested to the following specifications: 

Main Switch : 

IEC/EN 60947-3 

 

Wall fixing / dimensions 

 

Torque settings and cable capacity 

ISOLATOR 

– 2,5 Nm – 50 mm² 

 

Earth points: 2,0 Nm 

– M5 bolt for cable lug 

 

Important: 

Tighten all connections to the specified torques, including factory made connections. 
The terminals are suitable for copper connections ONLY. 

 

Testing of the installation 

1.  After completion  of the  installation,  it  is essential that a test  is carried out in accordance  with the latest 

Edition of the BS7671 (IET Wiring Regulations). 

 

2.  It is important that the following are included in 1 above: 

Check  that  all  connectors,  are  fitted  correctly  and  all  screw  type  connections  are  tightened 
sufficiently. 

 

Warning 

– Intellectual Property Rights

 

Eaton wishes to make it clear that it owns intellectual property 
rights in the product which it manufactures (whether or not listed 
in this leaflet) and that it will take legal action against any party 
found to be manufacturing, using, or selling any article which 
infringes the company’s intellectual property. All marks in this 
document identified with an R symbol or a TM symbol adjacent 
to the mark are trademarks of Eaton.

 

 

The use to which this product is put and its place of installation is 
outside our control.

 

Particular care should therefore be taken to follow the 
instructions given here and to ensure their continued availability 
in conjunction with the use of the product.

 

 

No responsibility can be accepted by us if these instructions are 
disregarded. Further copies of these instructions and information 
concerning the installation and proper use of this product can be 
obtained by contacting the: Technical Services Department

 

Eaton Electric Limited

 

Grimshaw Lane

 

Middleton, Manchester M24 1GQ

 

United Kingdom

 

Customer Support Centre

 

UK tel: +44(0) 8700 545 333

 

UK fax: +44(0) 8700 540 333

 

email: [email protected]

 

www.eaton.com

 

© 2015 Eaton Corporation

 

All Rights Reserved

 

Form No. IL01900001U

 

October 2015

 

Reviews: